background image

Phone: +46 31-69 53 00   Fax: +46 31-29 32 91   info@calectro.com   www.calectro.com

UNIGUARD UG-2-A2 STAND-ALONE-UNIT

Smoke detector for duct installation.

- One-tube air sampling system

- Service alarm 

- Test hole on cover

- Simple installation

- Sensitive flow indication

- Filter for dusty environments

- Simple service and maintainance

- Installer-friendly connection of cables

- Foolproof mountage of sampling tube

- Reset button on front cover

- Built-in alarm relay

FUNCTION

Uniguard has been developed to detect smoke in ventilation 
ducts and combines a smoke detector and an adaptor system 
where both tube and housing are specially designed for 
optimum airflow through the smoke detector.
The system fulfils all the requirements for safe fire detection 
with airflow speeds from 0,2 m/s to 20 m/s. 

 

Uniguard has a built-in alarm relay to control fire-safety 
dampers, to stop ventilation fans, or to activate accoustic and 
optical alarms etc.
The service alarm let you know when maintenance is needed, 
before a false alarm occur.
The detector has a bayonet fitting to simplify mounting and 
removal.
A contaminated detector will result in increased sensitivity 
and false alarms. To avoid nuisance alarms the detector has 
a service alarm (green LED). This indicates that the detector 
should be cleaned.

BASIC PRINCIPLES FOR POSITIONING

For the airflow through the adaptor to be representative of the 
airflow in the ventilation duct, install the detector at a place 
where normally flow meters etc. should be mounted, please 
see our installation instructions.
You can also use your national or local rules for mountage 
according to "Methods for measuring airflow in ventilation 
systems".

ACCESSORIES
Filter:

  

 

F1-UG/10 

pack

Mounting bracket:

 UG-Beslag 

 

 

 

(For insulated/circular ducts)

Waterproof housing:

 

UG-SH for outdoors, in 

 

 

 

cold attics etc.

TECHNICAL DATA

Detector type: 

 Ionisation 

 

UG-2-A2I

 Optical 

 

UG-2-A2O

Voltage Supply:

 24VAC 

100 

mA 

±20%

Operating temperature:

 -10°C 

to 

+50°C

Maximum humidity:

 99% 

rH

Tested and approved
according to EN-54:

 

by LPC (England), VdS (Germany)

Service alarm:

 

Indicated with green LED

Fire alarm:

 

Indicated with red LED

Adaptor housing:

 ABS

Air sampling tube:

 Aluminium. 

Standard 

length

 

0,6 m. Hole diameter 35mm.

 

The length of the venturi pipe shall

 

be choosen based upon how wide

 

the ventilation duct is. The venturi

 

pipes are available in 3 lengths;

 

0,6, 1,5 and 2,8 m. When the ven-

 

tilation duct is wider than 0,6 m

 

(dia), the venturi pipe should pen-

 etrate 

the 

whole 

duct.

 

Please see enclosed sketch.

Shorten the pipe to correct length.

Insert the end plug.

Put on the end plastic
gasket.

Put on the rubber
gasket, TET 26-35.

Drill a hole 
Ø 50 mm.

NOTE!

Drill a hole
Ø 35 mm.

Diameter of the duct bigger
than 0,6 m. 
The venturi pipe should 
penetrate the whole duct.

Drill a hole
Ø 35 mm.

Max diameter of the duct 0,6 m.

Use the venturi pipe 0,6 m.
Shorten the pipe, if necessary.

For ducts with a ø of less than 0,6 m use the 0,6 m tube.
For ducts with a ø of between 0,6 m and 1,3 m use the 1,5 m tube.
For ducts which are larger than 1,4 m use the 2,8 m tube.

The venturi pipe shall not 
protrude more than 30 mm 
through the duct wall.

Reviews: