3
Separator
technical
specifications
Insulation
technical
specifications
Materials: - body:
epoxy resin coated steel
- air vent body:
brass EN 12165 CW617N
- air vent hydraulic seal:
EPDM
- air vent float:
PP
- int. element:
HDPE
- drain valve body:
brass EN 12165 CW617N
- magnetic induction of ring system:
0,26 T
Medium:
water, glycol solution non hazardous,
therefore excluded from the guidelines of 67/548/EC Directive
Max percentage of glycol:
50%
Max working pressure:
10 bar
Temperature range:
0–110°C
Threaded connections:
1”, 1 1/4”, 1 1/2”, 2” F with unions
Temperature probe connections:
1/2” F
Drain cock:
hose connections
Inner part
Material:
closed-cell expanded PE-X
Thickness:
20 mm
Density: - inner part;
30 kg/m
3
- outer part;
80 kg/m
3
Conductivity (ISO 2581):
- at 0°C;
0,038 W/(m·K)
- at 40°C; 0,045 W/(m·K)
Water vapour resistance coefficient (DIN 52615):
> 1.300
Temperature range:
0–100°C
Reaction to fire (DIN 4102):
Class B2