201-2001

heat interface unit

6

Technical Specification - Actuator of 2-port Control Valve

Materials: - base and cover:

PC G 10

Synchronous motor: 

Normally closed

Supply:

230 V - 50 Hz

Power consumption: 

6.5 W; 7 VA

Opening time:

70 to 75 s

Closing time:

5 to 7 s

Microswitch contacts rating: 

0.8A

Protection class:

IP 40

Max. ambient temperature:

40˚C

Complies with Directive:

72/23/EC and
89/336/EC

Length of power cable:

95 cm

Operation

With the electrical supply off, the actuator keeps the valve in the
closed position. 

When a temperature thermostat or other electrical device switches
the supply on, the actuator moves the disc in the valve into the open
position.

When the supply is turned off, the valve closes again due to the
action of a return spring.

Construction

Auxiliary microswitch

The actuator is fitted with a microswitch to operate devices such as,
for example, a circulating pump. The microswitch comes on when
the valve is 60% open.

Manual opening

The valve can be opened manually by moving
the lever to the lock open position. When the
power is restored the manual control is
automatically overridden.

Clip on actuator

A rapid clip-on system makes it easy to remove the actuator from
the body of the valve for maintenance or replacement operations. 

Operation

The actuator is fitted with a special mechanism for gradual
movement of the valve disc which prevents judder and vibration due
to the inertia of the gear motor.

Removing the actuator

1 Set the lever on the side of the actuator to the open position (or

to manual opening).

2 Press the open button on the side of the actuator and remove 

the actuator.

Fitting the actuator

1 Set the lever on the side of the actuator to the open position (or

manual opening).

2 Check that the actuator is correctly positioned with respect to 

the valve as determined by the different dimensions of the 
operating stem and the locking pin.

3 Press the open button fully down. Clip on the actuator and 

release the button.

Technical Specification - Differential Pressure Control Valve

Medium:

water, glycol solution

Max. percentage of glycol:

50%

Max. working pressure:

16 bar

Temperature range:

-10 to 120˚C

Diaphragm max. differential pressure:

6 bar

∆p setting range:

50 to 300 mbar
5 to 30 kPa

Connections

Capillary tube connection size:

G¹/8

Tightening torque:

4 to 7 Nm

Length of capillary Ø3 mm

1.5 m

∆p indicator

The operation of setting the ∆p
differential regulating valve is
simplified by the presence of the
mobile indicator (1) and the
graduated scale (2) in mbar on the
valve knob.

Shutting off the flow and maintaining the ∆p setting

It is possible to isolate the circuit controlled by the differential
regulating valve. 

The mechanism to stop the flow is built into the valve.

The circuit is shut off by inserting an
Allen wrench into the hole and
turning it fully clockwise. 

This allows the flow to be shut-off for
system maintenance without having
to reset the valves after re-opening.

1

2

1

2

2

3

Summary of Contents for altecnic 201-2001

Page 1: ...201 2001 heat interface unit Installation Operation Maintenance Instructions ...

Page 2: ... people 7 In the case of particularly hard or impure water there must be suitable provision for filtering and treating the water before it enters the device in accordance with current legislation Failure to do so may result the HIU becoming damaged or working incorrectly 8 Any use of the HIU other than it s intended use is prohibited 9 Any coupling of the device with other system components must be...

Page 3: ...ection has been made to the highest of standards under current legislation 6 Electrical installation only be carried out by a qualified technician in accordance with current requirements General Information Please leave the manual as a reference guide for the user Dispose of any packaging in an appropriate manner most of which can be recycled In this Installation Operation and Maintenance guide we ...

Page 4: ...201 2001 heat interface unit 3 Dimensions DISCONNECT POWER SUPPLY BEFORE REMOVING COVER 400 600 160 65 75 5 74 G G G1B G1B 43 514 12 Depth of backplate 45mm Depth overall 185mm G ...

Page 5: ...tube for DPCV 3 Mounting bracket 11 Blanking cap 4 Flushing bypass with off set connections 12 Tee piece 5 Female union ball valve 13 1 hexagon nipple 6 Female union ball valve with drain 14 2 port control valve 7 DPCV 15 ball valve 8 Spool piece DISCONNECT POWER SUPPLY BEFORE REMOVING COVER 1 2 3 3 3 4 5 6 7 8 5 9 10 11 12 13 14 15 ...

Page 6: ... malfunctioning and hazards If the device is enclosed inside or between cabinets sufficient space must be provided for routine maintenance procedures It is recommended that electrical devices are NOT placed underneath the HIU as they may be damaged in the event of leakage from any hydraulic component of connection If this advice is not heeded the manufacturer cannot be held responsible for any resu...

Page 7: ...s judder and vibration due to the inertia of the gear motor Removing the actuator 1 Set the lever on the side of the actuator to the open position or to manual opening 2 Press the open button on the side of the actuator and remove the actuator Fitting the actuator 1 Set the lever on the side of the actuator to the open position or manual opening 2 Check that the actuator is correctly positioned wi...

Page 8: ...E O E Altecnic Limited 2017 ALTECNIC Differential Pressure Control Valve Continued Locking sealing the regulated position On the knob and on the valve body there are special holes that can be used to seal the devices once the regulation operations have been completed The application of sealing means that during any inspections it can be easily seen if the system has not been tampered with Seal ...

Reviews: