ELECTRICAL - ELECTRONIC OPTIONS

7558

25

  

Generic pulse input acquisition 

The CONTECA

®

 EASY module can acquire

 up to two additional 

pulse inputs

 (for one additional pulse a product code 755825 must 

be ordered; for two additional pulses 2 x product code 755825 are 
required), in addition to those already dedicated to DHW and DCW.
Sometimes, and normally when there is a controller code 755010, 
it is interesting to use the bus to transfer the user data in terms of 
consumption (gas meter / electricity meter).
The generic pulse must 

have no potential (voltage-free contact, 

maximum frequency 1 Hz

). Class IB. Residences and hotels are 

particularly suitable types of consumers.

7558

10

  Cooling units metering

Upon activation of the software module, CONTECA

®

 EASY is able to 

meter the heating and cooling units, on the evaluation of the 
temperature difference reversal, in separate registers for 

both 

the current values and for the logged files.

7558

8.

   Pulse output

The pulse output enables transferral of the heating and/or cooling 
energy values to a generic logger. 

The pulse weighs 1 kWh

.

The pulse output with no potential is 

open collector

 with pulse time 

120 ms - Vmax 24 V (dc) - 50 mA.

7558

90

   Remote energy totaliser

Electronic 8-digit LCD totaliser equipped with cover plate for 

three-

slot recessed electric box

.

Lithium battery: life 8 years - max frequency 20 Hz
Suitable for pulse outputs code 75588.
Shielded cable length (2x1 mm

2

): max 75 m.

7558

81

7558

82

Single pulse output - HEATING UNITS
Double pulse output - HEATING/COOLING UNITS

Code

RS485

EASY

CO

N

TECA

EASY

RS485

EASY

CO

N

TECA

EASY

7507 . .

755882

755881

Acquisition board

Terminals  2  -  3  Heating units

7507 . .

Terminals  2 -  3  Heating units

Terminals  1 -  2  Cooling units

CALEFFI

ENERGY kWh

2

6

0 V

HEATING UNITS output

COOLING UNITS output

GND

12

34

56

78

91
01
11
21
31
41
51
61
71

8

Option code 755826 is supplied with an AUTOFLOW

®

 with a 

1/2” connection and a nominal flow rate of 40 l/h, code 127141 

M04

7558

26

Flow rate - DHW recirculation scan

In compliance with standard 9182 for DHW systems with recirculation 

on the risers, recirculation pipes may also need to be laid inside the user 

systems. DHW consumption meters are therefore vulnerable to incorrect 

circulation, which leads to errors in total consumption readings (actual 

user information). The scan option can be used to distinguish between 

actual and incorrect (or gross) flow rates, providing an exact DHW 

consumption value for the division of expenses. The option must be 

linked to the CONTECA

®

 EASY heat meter supply; its on-site application 

and setup must be carried out by Caleffi technicians or staff from an 

authorised service centre. 

The option requires setting of a recirculation flow rate (threshold), if 

drawing does not take place. Every time the detected flow rate is lower 

than the set threshold, only the GROSS register is increased, while - 

when the flow rate is above the threshold - both registers (GROSS 

and NET) are increased.

The following appear on the display:

 

- NET consumption

 

- GROSS consumption

 

- DHW flow rate

  1

       m

3

  1

       m

3

 G

       m

3

/h

To maintain a constant recirculation flow rate, a flow rate limiter with a 

setting value under 100 l/h must be fitted to the return branch of the 

apartment recirculation network. Furthermore, a specific flow meter 

must be used, with a pulse weight of 1 litre (see code 794204/C1 and 

code 794205/C1).

Application diagram, code 755826

13

Summary of Contents for CONTECA EASY ULTRA

Page 1: ...culator unit an ultrasonic flow meter and two temperature probes The CONTECA EASY ULTRA meter is extremely simple to install and requires no special maintenance The flow is measured using the two way...

Page 2: ...h l h l h C kWh PN Qp Qi Qs m m C K C 90 preferably horizontal class OA OC in accordance with EN1434 2 see table 1 and 2 see table 1 and 2 see table 1 and 2 lithium battery life 12 years p Code The CO...

Page 3: ...e while the return probe blue label should be on the return pipe At the end of the installation process the main heat meter components electronics unit temperature probes and volume meter should under...

Page 4: ...protect the volume meter By observing the instant flow rate and flow return temperature difference values significantly lower flow rate compared to the nominal value and significantly higher temperat...

Page 5: ...duration 120 ms Vmax 24 V dc 50 mA 755882 2 3 OUT 1 Open collector pulse output for HEATING units GND 2 duration 120 ms Vmax 24 V dc 50 mA 755881 755882 4 NOT used 5 6 IN 4 fourth pulse input generic...

Page 6: ...input blue wire white wire Enery pulse outputs codes 755881 755882 2 3 Remote heating units totaliser output kWh OC type 1 2 Remote cooling units totaliser output kWh OC type These outputs can be conn...

Page 7: ...ption with optional code 755826 2nd DCW pulse consumption 3rd pulse consumption with optional code 755825 Flow rate Power Flow temperature Return temperature Temperature difference DHW flow rate with...

Page 8: ...change K V volume change l V N P where N number of pulses P single pulse value per litre Operating specifications 1 In order to protect against spurious measurements or undesired metering the meterin...

Page 9: ...ass the thread through the hole on the probe and the pocket and twist it E Wind the thread as illustrated in the figure so that once lead sealing is complete the cap cannot be unscrewed without breaki...

Page 10: ...bob D Pass the thread through the hole on the probe and the pocket and twist it E Wind the thread as illustrated in the figure so that once lead sealing is complete the cap cannot be unscrewed without...

Page 11: ...SY RS485 EASY CONTECA EASY RS485 EASY CONTECA EASY RS485 EASY CONTECA EASY RS485 EASY CONTECA EASY RS485 EASY CONTECA EASY 11 M Bus M Bus Master 230 V ac 755058 M Bus RS 485 slave converter Used to ad...

Page 12: ...ied out by the user removed Maximum number of users 250 Datalogger specifications Electric supply 24 V dc 10 24 V ac 3 W 2 Ethernet outputs ETH1 PoE ETH2 Working temperature range 0 50 C Mounting 35 m...

Page 13: ...755881 Acquisition board Terminals 2 3 Heating units 7507 Terminals 2 3 Heating units Terminals 1 2 Cooling units CALEFFI ENERGY kWh 2 6 0 V HEATING UNITS output COOLING UNITS output GND 1 2 3 4 5 6...

Page 14: ...20030 PULSE MONITOR Pulse logger Electric supply lithium battery 6 digit display with user key Daily data saving Tamper proof seal and sensor Enables acquisition of a pulse output from the heat meter...

Page 15: ...ues with the aim of providing the exact domestic hot water consumption figure Code 755890 Electronic 8 digit LCD totaliser equipped with cover plate for three slot recessed electric box Lithium batter...

Page 16: ...ULTRA 7507 series CONTECA EASY ULTRA heat meters in the 7507 series conform to the requirements of directive 2014 32 EU better known as MID acronym for Measuring Instrument Directive Production proce...

Reviews: