16
Appendix 6. LEGIOMIX_6000_SERIES MODBUS RTU MAPPINGS TO BACNET
Point Name
BACnet Object Type
BACnet Object ID
Description
Product type
AV
1
6001
ID Modbus
AV
2
1...247
Tmix Deg_C (Mixing temp.)
AV
3
°C
Trec Deg_C (Recirculation temp.)
AV
4
°C
Tmix Deg_F (Mixing temp.)
AV
5
°F
Trec Deg_F (Recirculation temp.)
AV
6
°F
State
AV
7
1 - Regulation
2 - Disinfection
3 - Flushing
4 - Thermal shock
5 - Alarm
Program ID
AV
8
0 - 0
1 - 1a
2 - 1b
3 - 2
Current Day
AV
9
1...31
Current Month
AV
10
1...12
Current Year
AV
11
2017...
Current Hour
AV
12
0...23
Current Minute
AV
13
0...59
Language
AV
14
0 - IT
1 - EN
2 - FR
3 - DE
4 - ES
5 - PT
6 - NL
7 - SL
8 - HR
9 - SR
10 - RO
Time ON (Start dis.)
AV
15
0...23 (h)
Time ON (m) (Start dis.)
AV
16
0...59 (min)
Time OFF (h) (Stop dis.)
AV
17
0...23 (h)
Time OFF (Stop dis.)
AV
18
0...59 (min)
Time Wait (before reading rec.)
AV
19
1...255 (min)
Time min (to have correct dis.)
AV
20
0...254 (min)
Time Flux (Time of closing relay 4
after ending the dis.)
AV
21
0...2550 (sec)
Time Shock (Time of duration)
AV
22
1...4320 (min)
Set Reg Deg_C (Set Mix temp)
AV
23
20...85 (°C)
Set Dis Deg_C (Set Dis temp)
AV
24
40...85 (°C)
Set Ric Deg_C (Set Rec temp)
AV
25
40...85 (°C)
Set Shock Deg_C (Set Shock temp)
AV
26
30...85 (°C)
Set Tmax Deg_C (Set max temp)
AV
27
50...90 (°C)
Set Reg Deg_F (Set Mix temp)
AV
28
68...185 (°F)
Set Dis Deg_F (Set Dis temp)
AV
29
104...185 (°F)
Set Ric Deg_F (Set Rec temp)
AV
30
104...185 (°F)
Set Shock Deg_F (Set Shock temp)
AV
31
86...185 (°F)
Set Tmax Deg_F (Set max temp)
AV
32
122...194 (°F)
Daily Disinfection
AV
33
bit 0 : Monday
bit 1 : Tuesday
bit 2 : Wednesday
bit 3 : Thursday
bit 4 : Friday
bit 5 : Saturday
bit 6 : Sunday