5

Heat meter installation

The HIU is designed to fit a compact heat meter (with incorporated

return probe) with 1” threaded connections and 130 mm gauge.

Before carrying out any maintenance, repair or part replacement

work, proceed as follows:

- cut off the electric supply

- remove the cover

- close the shut-off valves

- empty the HIU using the drain cocks provided

Proceed as described below to install the heat meter:

- remove the template (A)

- remove the cap (B)

- install the flow meter on the return pipe

- install the flow probe in the M10 pocket (B) 

Please  refer  to  the  heat  meter  technical  data  sheets  for  further

information.

A

B

Hydraulic connections

Hydraulic connections to the centralised line must be implemented

using the manual shut-off valves supplied with the HIU, which allow

any necessary maintenance work to take place without having to

empty the centralised system.

It is advisable to install manual shut-off valves (not supplied) also

on the bottom connections to the apartment circuits.

Before installation, it is recommended to carry out accurate flushing

of  all  the  pipes  of  the  system  in  order  to  remove  any  residue  or

impurities that could endanger correct operation of the HIU.

In  order  to  facilitate  these  operations  a  manual  bypass  flushing

valve is available (code 789100).

N.B. Install the valves as shown in the figure

N.B.:

1 Install water hammer arresters to compensate for any overpressure in the domestic water circuit;

2 In the presence of hot water recirculation or if a non-return valve is fitted into the domestic cold water inlet, provision must be made to accomodate the expansion

of the water contained within the system and the heat interface unit;

3 All hydraulic connections must be checked before pressurising the system. Vibration during transport may cause the connections to become loose. DO NOT APPLY

EXCESSIVE TIGHTENING TORQUE otherwise the components may be damaged.

Summary of Contents for SATK20 Series

Page 1: ...ms Product range SATK20103HE Direct wall mounted HIU for LOW temperature heating instantaneous domestic hot water production power capacity 40 kW SATK20203HE Direct wall mounted HIU for MEDIUM tempera...

Page 2: ...high intensity electromagnetic fields This device cannot be used in areas at risk of explosion or fire 3 The device must be connected to an independent bipolar switch If work has to be done on the de...

Page 3: ...ell cover EPP Heat exchanger brazed stainless steel SATK20305 technical specifications Medium water Maximum percentage of glycol 30 Maximum medium temperature 85 C Maximum working pressure primary cir...

Page 4: ...ontact a qualified technician to request a thorough check of the electrical system Electrical safety of the appliance is only achieved when it is correctly connected to an effective earthing system ma...

Page 5: ...centralised system It is advisable to install manual shut off valves not supplied also on the bottom connections to the apartment circuits Before installation it is recommended to carry out accurate...

Page 6: ...r steady illumination of the LEDs ON Electric supply 230 V ac DHW Domestic cycle CH Heating cycle FAULT Fault detected Domestic cycle Heating cycle Operating principle All heating and domestic hot wat...

Page 7: ...lty safety valve is working properly again Thermal safety valve fault SATK20103HE LOW temperature Error code 76 76 Removing a fault Normal operating conditions are restored automatically once the faul...

Page 8: ...ner heat meter flow probe pocket 18 Primary circuit shut off valves SATK20103HE LOW temperature heat interface unit with high efficiency pump Functional characteristics Heating range 45 75 C Set point...

Page 9: ...a temperature of 45 C Once the maximum set point has been reached the function is executed following the same procedures in reverse from the maximum set point to the minimum set point This function h...

Page 10: ...ctory settings 1 2 3 4 5 6 4 ON Functional characteristics Maximum heating temp 85 C ON OFF regulation DHW production range 42 60 C Optional functions Domestic cycle DHW pre heating function 1 2 3 4 5...

Page 11: ...circulate at the temperature supplied by the central heating system ON OFF regulation The valve is closed on completion of the heating cycle The active heating cycle is signalled by lighting of the ye...

Page 12: ...inserted Replacing the valve actuator Disconnect the actuator cable lightly pressing the tab on the connector and extracting it see page 13 ref 4 8 Extract the fixing clip D and then the actuator Posi...

Page 13: ...pulito Room thermostat Volt free connection This connection may not be available To be wired during installation Room thermostat not supplied potential free line MAX 30 m 6 ON Dip switch 6 configurati...

Page 14: ...d heat exchanger partly clogged call qualified personnel to have it serviced modulating valve actuator faulty call qualified personnel to have it replaced valve obturator blocked in intermediate posit...

Page 15: ...ced primary circuit flow rate insufficient contact person in charge of system centralised system not working contact person in charge of system CH LED off chrono thermostat time setting incorrect chec...

Page 16: ...ve result Are the connections compliant with specifications and made in accordance with best practices 13 all Are the shut off valves open 14 all Has the visual inspection of the hydraulic connections...

Reviews: