Heating function

DEFAULT SETTING: set point regulation
(technical parameter t01 = 0)

When heating cycle activation is requested by the room thermostat, 

the circulation pump is powered while the modulating valve is opened 

gradually until the set point temperature is reached. In the high 

temperature models (SATK2230. - SATK2240.) the valve is opened 

up to the maximum allowed (see “primary flow rate limitation” on 

page 14).

The circulation pump is stopped and the modulating valve is closed at 

the end of the heating cycle. The heating cycle ON condition is indicated 

by the blinking

 

     symbol.

Heating flow temperature setting (SATK2210. and SATK2220.)

To set the flow temperature press the <SET> key until the symbol in 
the red circle appears. Use the <R> knob to change the value.
The flow temperature range is:
25–45°C  for SATK2210. (LOW temperature)
45–75°C  for SATK2220. (MEDIUM temperature)

OPTIONAL SETTING: primary return temperature limit 
(technical parameter t01 = 1)

When heating cycle activation is requested by the room thermostat, 

the circulation pump is powered while the modulating valve is opened 

gradually until the set point temperature is reached (in SATK2230. 

and SATK2240. the vale is open fully, up to the maximum allowed), if 

the return temperature is lower than or equal to the set limit value. In 

case this condition is not met, in HIUs with control of the flow temp. 

(SATK2210. and SATK2220.) the flow temperature is reduced (by a 

maximum of 15°C in SATK2220., and maximum 3°C in SATK2210., in 

order to bring return temperature within the limit values. In SATK2230. 

and SATK2240. a reduction of the heating flow rate is operated. When 

the flow temperature/flow rate must be reduced in order to limit return, 

the 

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

 icon appears on the display.

To set the flow temperature press the <SET> button until the symbol 
in the green circle appears. Use the <R> knob to change the value (*).
The primary return limit temperature range is:
15–42°C  for SATK2210. (LOW temperature)
30–70°C  for SATK2220. (MEDIUM temperature)

OPTIONAL SETTING: modulating temperature regulation with 
compensated set point (technical parameter t01 = 2)
(SATK2210. and SATK2220.)

When the function is enabled, the flow temperature is modified 

 

(± 10°C with respect to the set point for HIU in HIGH temperature,  
± 3°C if in LOW temperature) according to the temperature detected 
by the return probe in order to maintain this latter temperature value 
constant. This keeps the actual thermal output of the slab under 
control, and consequently also the ambient thermal load. The thermal 
response time of the system is thus minimised.
This feature should not be used in combination with thermostatic 
radiator valves.
When the function is enabled the display shows the symbol     .

OPTIONAL SETTING: weather compensation (technical 
parameter t01 = 3)

When the function is enabled, the flow temperature is calculated 
based on the temperature detected by the outside probe (optional 
code 789833), in accordance with the curve shown below. The “k” 
coefficient can be changed by pressing <SET> button until the related 
setting appears.

The display shows the symbol 

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

.

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

(*) if these set points cannot be changed you must set parameter 
t07 to value 0 in the technical menu (see “access to technical menu” 
below). Parameter t07 = 1 “freezes” the operating set points to 
prevent inadvertent modifications by the user.

Text (°C)

T flow (°C)

MIN

5

0

-5

-15

MAX

10

-10

20

15

25

30

-20

k = 3.0

k = 2.5

k = 2.0

k = 1.5

k = 1.0

k = 0.5

k = 0.0

MAX is the set temperature value

MIN is 45°C for HIGH temp. HIUs, 25°C for LOW temp. ones.

<mode>

ACS ON/OFF
Risc. ON/OFF

<set>

Ora/giorno corrente
Temperature di set point
k regolazione climatica

<day/night>

Set diurno/notturno

<temp>

Visualizzazione 
temperature
(set point am 
sonde)

<prog>

Programmazione oraria 
riscaldamento e funzione 
“comfort”

<reset>

Reset errore riarmabile/funzione 
scaldamassetto

<R>

+/-

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

Summary of Contents for SATK22107

Page 1: ...mestic hot water capacity 50 kW 1 With primary pump SATK22405 Direct wall mounted HIU for HIGH temp heating Domestic hot water capacity 60 kW 1 With primary pump SATK22407 Direct wall mounted HIU for...

Page 2: ...acteristics of both units into consideration 10 An combination coupling could compromise the operation of the device and or system IMPORTANT Risk of electric shock Live parts Shut off the electric sup...

Page 3: ...primary circuit Dp 600 kPa 6 bar Domestic water circuit max flow rate 24 l min 0 4 l s Minimum flow rate to activate domestic water flow meter 2 l min 0 3 Electric supply 230 V ac 10 50Hz Max power c...

Page 4: ...r primary circuit air vent Characteristic components SATK2210 LOW temperature Hydraulic diagram SATK2210 and SATK2220 TS TA 2 V V V V V V 3 4 7 12 13 5 6 8 9 10 11 21 14 15 19 24 20 17 16 17 22 23 25...

Page 5: ...draulic diagram SATK2230 and SATK2240 TS TA 2 V V V V V V 3 4 7 12 13 5 6 8 9 10 11 21 14 15 19 24 20 17 16 17 22 23 25 TA 2 V V V V V V 3 4 7 5 6 8 9 10 11 21 13 14 19 22 20 23 16 17 18 SATK2210 only...

Page 6: ...out template code 789023 Hydraulic installation Preliminary operations installation without template After having established the point of installation of the appliance perform the following operation...

Page 7: ...bottom Connections on the top Heat meter installation The HIU is fitted to house a compact heat meter with incorporated return probe with 1 threaded connections and length of 130 mm Before carrying o...

Page 8: ...directed toward the exterior of the HIU using the pathways provided in the insulation and on the frame All the low voltage lines must be routed through a single dedicated cable raceway using the path...

Page 9: ...ntrol Refer to the dedicated user manual for the procedure Filling the central heating system Open the shut off valves on the connections to the centralised line and in the central heating system proc...

Page 10: ...riarmabile funzione scaldamassetto R mode ACS ON OFF Risc ON OFF set Ora giorno corrente Temperature di set point k regolazione climatica day night Set diurno nottu prog Programmazione oraria riscalda...

Page 11: ...oint k regolazione climatica day night Set diurno notturno temp Visualizzazione temperature set point ambiente sonde prog Programmazione oraria riscaldamento e funzione comfort reset Reset errore riar...

Page 12: ...ed the display shows the symbol OPTIONAL SETTING weather compensation technical parameter t01 3 When the function is enabled the flow temperature is calculated based on the temperature detected by the...

Page 13: ...menu see access to technical menu below Parameter t07 1 freezes the operating set points to prevent inadvertent modifications by the user The comfort function can be alternatively preheating of the DH...

Page 14: ...ntrolling the maximum opening of the primary circuit modulating valve Since latter is controlled by a differential pressure limiter it is possible to supply direct correspondence between the opening p...

Page 15: ...wo seconds and then press the same key repeatedly until reaching the required characteristic refer to the figure below Having identified the required characteristic head flow rate chart shown below wa...

Page 16: ...xternal primary flow pump normally OFF The contact must be closed if any HIU function is active DHW production heating pre heating Parameter t05 must be set to 1 2 4 7 example 2 Distinction of consump...

Page 17: ...ire twisted cable Compliance with this requirement becomes even more significant the more extensive the RS 485 network If alternatively a shielded wire is used the shield must be connected solely on t...

Page 18: ...code 76 Corrective action Normal operating conditions are restored automatically once the faulty safety valve works properly again reriscaldo circolo Impostazione default limitazione portata massima...

Page 19: ...PAID AUX RS 4 IN IN IN OUT IN OUT EXP PORT OTS RT PREPAID AUX RS 485 BUS IN IN IN OUT IN OUT EXP PORT OTS RT PREPAID AUX RS 485 BUS IN IN IN OUT IN OUT EXP PORT OTS RT PREPAID AUX RS 485 BUS IN IN IN...

Page 20: ...pty the heat interface unit using the drain cocks provided Exchanger replacement As a preliminary step remove the flow sensor refer to replacing the DHW priority flow meter on page 21 and position it...

Page 21: ...e previous paragraph Extract the obturator unscrewing the locking nut F Replace the obturator screw on the locking nut F and then fit the actuator Insert the fixing clip respecting the correct directi...

Page 22: ...ature set point disable the function primary circuit strainer of the HIU clogged call qualified personnel to have it serviced exchanger partly clogged call qualified personnel to have it serviced modu...

Page 23: ...on in charge of system electronic regulator not working call qualified personnel to have it replaced primary circuit flow rate insufficient contact person in charge of system centralised system not wo...

Page 24: ...if required been carried out 13 Has the remote user interface been configured for installation on board thermostat function disabled inside the apartment with thermostat function enabled 14 Have the h...

Reviews: