FAULT DESCRIPTION

ALERTS

POSSIBLE CAUSE OF FAULT

OPERATIONS TO BE PERFORMED

The room 

does not reach 

the desired 

temperature

blinking 

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

  

icon

heating cycle temperature set point too low

increase set point

chrono-thermostat temperature setting incorrect

check programming of chrono-thermostat

HIU strainer clogged

call qualified personnel to have it serviced

primary return temperature limitation intervention (the 

following icon appears 

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

 )

change the return temperature set point/

disable the function

primary flow rate in heating mode set at an excessively low 

limit

change heating valve opening limit

heating valve actuator faulty

call qualified personnel to have it replaced

heating valve obturator blocked

call qualified personnel to have it replaced

modulating valve actuator connector disconnected

reconnect actuator connector

DHW temperature probe cable inverted with heating probe

restore correct connection

presence of air in the system

vent the system

pump not working

call qualified personnel to have it replaced

pump cable not connected

restore connection

possible system shut-off valves/terminals closed

open the valves

centralised system temperature insufficient

contact person in charge of system

electronic regulator not working

call qualified personnel to have it replaced

primary circuit flow rate insufficient

contact person in charge of system

centralised system not working

contact person in charge of system

thermostat function enabled on the remote user interface 

when it should be disabled

contact person in charge of system

fixed 

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

  

icon 

chrono-thermostat time setting incorrect

check programming of chrono-thermostat

chrono-thermostat not working

check chrono-thermostat

thermostat function disabled on the remote user interface

contact person in charge of system

display is off

Electric supply cut off

restore HIU electric supply

Protection fuse burnt out

call qualified personnel to have it replaced

icon 

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

  

absent

Heating not enabled (summer mode)

enable heating by means of heat interface 

unit

error code 4 active

heating circuit pressure too low

restore system pressure

error code 5 active

heating temperature probe faulty

call qualified personnel to have it replaced

error code 15 active

compensation temperature probe faulty

call qualified personnel to have it replaced

error code 38 active

external temperature probe faulty/not connected

call qualified personnel to have it replaced

error code 69 active

safety thermostat cut-out

press the reset button/call qualified 

personnel to have it serviced

error code 80 active

no credit

top-up prepaid system

Summary of Contents for SATK22107

Page 1: ...mestic hot water capacity 50 kW 1 With primary pump SATK22405 Direct wall mounted HIU for HIGH temp heating Domestic hot water capacity 60 kW 1 With primary pump SATK22407 Direct wall mounted HIU for...

Page 2: ...acteristics of both units into consideration 10 An combination coupling could compromise the operation of the device and or system IMPORTANT Risk of electric shock Live parts Shut off the electric sup...

Page 3: ...primary circuit Dp 600 kPa 6 bar Domestic water circuit max flow rate 24 l min 0 4 l s Minimum flow rate to activate domestic water flow meter 2 l min 0 3 Electric supply 230 V ac 10 50Hz Max power c...

Page 4: ...r primary circuit air vent Characteristic components SATK2210 LOW temperature Hydraulic diagram SATK2210 and SATK2220 TS TA 2 V V V V V V 3 4 7 12 13 5 6 8 9 10 11 21 14 15 19 24 20 17 16 17 22 23 25...

Page 5: ...draulic diagram SATK2230 and SATK2240 TS TA 2 V V V V V V 3 4 7 12 13 5 6 8 9 10 11 21 14 15 19 24 20 17 16 17 22 23 25 TA 2 V V V V V V 3 4 7 5 6 8 9 10 11 21 13 14 19 22 20 23 16 17 18 SATK2210 only...

Page 6: ...out template code 789023 Hydraulic installation Preliminary operations installation without template After having established the point of installation of the appliance perform the following operation...

Page 7: ...bottom Connections on the top Heat meter installation The HIU is fitted to house a compact heat meter with incorporated return probe with 1 threaded connections and length of 130 mm Before carrying o...

Page 8: ...directed toward the exterior of the HIU using the pathways provided in the insulation and on the frame All the low voltage lines must be routed through a single dedicated cable raceway using the path...

Page 9: ...ntrol Refer to the dedicated user manual for the procedure Filling the central heating system Open the shut off valves on the connections to the centralised line and in the central heating system proc...

Page 10: ...riarmabile funzione scaldamassetto R mode ACS ON OFF Risc ON OFF set Ora giorno corrente Temperature di set point k regolazione climatica day night Set diurno nottu prog Programmazione oraria riscalda...

Page 11: ...oint k regolazione climatica day night Set diurno notturno temp Visualizzazione temperature set point ambiente sonde prog Programmazione oraria riscaldamento e funzione comfort reset Reset errore riar...

Page 12: ...ed the display shows the symbol OPTIONAL SETTING weather compensation technical parameter t01 3 When the function is enabled the flow temperature is calculated based on the temperature detected by the...

Page 13: ...menu see access to technical menu below Parameter t07 1 freezes the operating set points to prevent inadvertent modifications by the user The comfort function can be alternatively preheating of the DH...

Page 14: ...ntrolling the maximum opening of the primary circuit modulating valve Since latter is controlled by a differential pressure limiter it is possible to supply direct correspondence between the opening p...

Page 15: ...wo seconds and then press the same key repeatedly until reaching the required characteristic refer to the figure below Having identified the required characteristic head flow rate chart shown below wa...

Page 16: ...xternal primary flow pump normally OFF The contact must be closed if any HIU function is active DHW production heating pre heating Parameter t05 must be set to 1 2 4 7 example 2 Distinction of consump...

Page 17: ...ire twisted cable Compliance with this requirement becomes even more significant the more extensive the RS 485 network If alternatively a shielded wire is used the shield must be connected solely on t...

Page 18: ...code 76 Corrective action Normal operating conditions are restored automatically once the faulty safety valve works properly again reriscaldo circolo Impostazione default limitazione portata massima...

Page 19: ...PAID AUX RS 4 IN IN IN OUT IN OUT EXP PORT OTS RT PREPAID AUX RS 485 BUS IN IN IN OUT IN OUT EXP PORT OTS RT PREPAID AUX RS 485 BUS IN IN IN OUT IN OUT EXP PORT OTS RT PREPAID AUX RS 485 BUS IN IN IN...

Page 20: ...pty the heat interface unit using the drain cocks provided Exchanger replacement As a preliminary step remove the flow sensor refer to replacing the DHW priority flow meter on page 21 and position it...

Page 21: ...e previous paragraph Extract the obturator unscrewing the locking nut F Replace the obturator screw on the locking nut F and then fit the actuator Insert the fixing clip respecting the correct directi...

Page 22: ...ature set point disable the function primary circuit strainer of the HIU clogged call qualified personnel to have it serviced exchanger partly clogged call qualified personnel to have it serviced modu...

Page 23: ...on in charge of system electronic regulator not working call qualified personnel to have it replaced primary circuit flow rate insufficient contact person in charge of system centralised system not wo...

Page 24: ...if required been carried out 13 Has the remote user interface been configured for installation on board thermostat function disabled inside the apartment with thermostat function enabled 14 Have the h...