background image

14

Primary flow rate limitation

(*) The correspondence between valve position and flow rate is indicative. Graphs obtained with pressure head upstream of the HIU = 50 kPa.

N.B. Any limitation must be assessed in accordance with the effective thermal characteristics of the residential unit served.

Anti-legionella function

 

 

 

 

 

 

 

 

   

 

 

 

 

 

Primary flow rate limitation in heating mode

DEFAULT  SETTING:  no  limitation  (technical  parameter  t03  =
100)

During  start-up  of  the  heating  cycle  from  cold,  e.g.  on  changeover
from  night-time  ambient  set  point  to  the  daytime  set  point,  the  HIU
may  demand  a  significantly  higher  primary  flow  rate  than  the  design
one, because of the low temperatures of the secondary medium. This
effect is far greater with high temperature systems in which, during the
transient to the design operating condition, high thermal power values
may  be  transferred  from  the  primary  circuit  to  the  secondary  circuit.
This effect can be restricted by lengthening the transient, setting a limit
on the maximum primary flow rate that can be withdrawn in heating
mode.

The  flow  rate  limitation  is  imposed  by  controlling  the  maximum
opening  of  the  primary  circuit  modulating  valve.  Since  latter  is
controlled  by  a  differential  pressure  limiter,  it  is  possible  to  supply
direct correspondence between the opening position of the valve and
the circulating flow rate (*)

Primary flow rate limitation in DHW mode

DEFAULT  SETTING:  no  limitation  (technical  parameter  t04  =
100)

Likewise, you can establish a limit to the primary flow rate that can be
tapped for instantaneous DHW production.

The  flow  rate  limitation  is  imposed  by  controlling  the  maximum
opening  of  the  primary  circuit  modulating  valve.  Since  latter  is
controlled  by  a  differential  pressure  limiter,  it  is  possible  to  supply
direct correspondence between the opening position of the valve and
the circulating flow rate (*)

A  maximum  degree  of  opening  (%)  can  be  set  via  technical  menu
parameter t03.

A  maximum  degree  of  opening  (%)  can  be  set  via  technical  menu
parameter t04.

Max opening (%)

Fl

o

w

 r

a

te

 (

l/

h)

70

60

50

80

100

90

0

200

400

600

800

1000

1200

 

 

 

 

 

 

 

 

Max opening (%)

Fl

o

w

 r

a

te

 (

l/

h)

70

60

50

80

100

90

0

200

400

600

800

1000

1200

DEFAULT SETTING: anti-legionella function OFF
(technical parameter t08 = 0)

Enabling the anti-legionella function by means of technical parameter
t08 = 1, in time band 3:00 - 3:30:

-  the  DHW  set  point  will  be  temporarily  increased  to  the  maximum
value (60°C) - the comfort/recirculation function will be forced ON.

As  a  result  of  the  temperature  rise  of  the  set  point,  at  time  3:00  a
comfort function (either pre-heating or recirculation) will be triggered,
bringing the temperature to a value close to 60°C, such as to rapidly
reduce the presence of any bacteria.

During execution of the cycle, the user interface display will show the
blinking 

symbol (refer to the adjacent figure).

IMPORTANT!
- Any DHW production that occurs during the time band (3:00 -
3:30) will be at 60°C.
- The cycle execution time band (3:00 - 3:30) is established in
accordance  with  the  time  set  on  the  remote  control  unit.
Incorrect  time  setting  will  result  in  execution  of  the  anti-
legionella function in a different actual time band.
Due to the effect of exchanger thermal inertia, temporary DHW
production at high temperature could proceed also beyond the
time of 3:30.

If the function is enabled thermostatic mixing valves should be
installed on the users level (washbasin/shower, etc.).

Summary of Contents for SATK32 Series

Page 1: ...de 10 Commissioning 9 Electrical installation 8 Hydraulic installation 5 Hydraulic components and diagram 4 Dimensions Technical specifications 3 Safety instructions 2 DHW function Comfort functions P...

Page 2: ...k must be carried out on the device cut off the electric supply first Do not use devices with automatic or time reset or which may be reset accidentally 4 Use suitable automatic protection devices in...

Page 3: ...nimum flow rate to activate domestic water flow meter 2 l min 0 3 Electric supply 230 V ac 10 50Hz Max power consumption 80 W Protection class IP 40 Pump UPM3 15 70 Actuators 24 V stepper motor Probes...

Page 4: ...be 10 Pressure gauge 11 Safety thermostat 12 130 mm heat meter template 13 1 4 F pressure test port 14 Connection for M10x1 heat meter return probe 15 Primary drain cock 16 Connection for M10x1 heat m...

Page 5: ...kflow preventer code 572120 proceed as follows remove the nuts shown in the figure with letter A Hydraulic installation Preliminary operations installation without template After having established th...

Page 6: ...tem in order to remove any residue or impurities that could endanger correct operation of the HIU In order to facilitate these operations a manual bypass flushing valve is available code 789110 N B In...

Page 7: ...pipe To tighten the nuts apply maximum tightening torque of 25 Nm taking account of the indications of the heat meter manufacturer install the flow probe in the M10 pocket B Please refer to the heat m...

Page 8: ...directed toward the exterior of the HIU using the pathways provided in the insulation and on the frame All the low voltage lines must be routed through a single dedicated cable raceway using the path...

Page 9: ...necessary restore the pre charge value shown in the technical specifications Filling the user system SATK32 series HIU can be fitted with a charging unit equipped with a backflow preventer F check va...

Page 10: ...ng modes OFF DHW only summer mode Heating DHW winter mode Heating only Selecting set points current time and comfort function Press the set key repeatedly to set the current time set point temperature...

Page 11: ...arious parameters which can then be edited pressing and rotating knob R Technical parameter t00 Primary limit set return temperature in heating mode Primary limit set return temperature in DHW mode Co...

Page 12: ...ng To set the flow temperature press the SET key until the symbol in the red circle appears for the return temperature limit press the key until the symbols in the green circle are displayed Use the R...

Page 13: ...7 1 freezes the operating set points to prevent inadvertent modifications by the user The comfort function can be alternatively preheating of the DHW plate heat exchanger or management of DHW recircul...

Page 14: ...posed by controlling the maximum opening of the primary circuit modulating valve Since latter is controlled by a differential pressure limiter it is possible to supply direct correspondence between th...

Page 15: ...es a sequence of LEDs showing the instantaneous power consumption 1 yellow LED lit power between 0 and 25 of Pmax 2 yellow LEDs lit power between 25 and 50 of Pmax 3 yellow LEDs lit power between 50 a...

Page 16: ...must be set to 1 2 4 7 This value t05 7 is set by default example 2 Distinction of consumption for DHW production from total consumption in combination with heat meter equipped with dedicated function...

Page 17: ...ire twisted cable Compliance with this requirement becomes even more significant the more extensive the RS 485 network If alternatively a shielded wire is used the shield must be connected solely on t...

Page 18: ...nd disabled Any requests to run cycles not associated to the previous one will continue to run normally Heating flow probe fault Error code 5 Domestic hot water probe fault Error code 6 Return probe f...

Page 19: ...o be interfaced with controllers managing the heating and DHW production services by means of pre paid type logic The HIU interprets an open contact as credit available Closing the contact disables th...

Page 20: ...ween 0 9 and 1 2 bar Restore the pressure value if necessary Re open the shut off valves and restore secondary circuit pressure to a value between 1 3 and 1 7 bar Check for the absence of any liquid d...

Page 21: ...tuator see previous paragraph Extract the obturator unscrewing the locking nut F Replace the obturator screw on the locking nut F and then fit the actuator Insert the fixing clip respecting the correc...

Page 22: ...r partly clogged call qualified personnel to have it serviced modulating valve actuator faulty call qualified personnel to have it replaced DHW temperature probe cable inverted with heating probe rest...

Page 23: ...in charge of system electronic regulator not working call qualified personnel to have it replaced primary circuit flow rate insufficient contact person in charge of system centralised system not work...

Page 24: ...s external sensor prepayment auxilliary microswitch Modbus if required been carried out 15 Has the remote user interface been configured for installation on board thermostat function disabled inside t...

Reviews: