INSTRUCTIONAL MANUAL
2750L-P/4500L-P/6000L-P
August, 2001
Rev. K
-54-
Table 3-12
PROGRAM HEADERS
HEADER
EXTENSION
ARGUMENT DEFINITION
AMP
A, B, C
# or numeric from 0.0 to RNG value Amplitude in volts.
CAL
A, B, C
0 to 255
Calibrate the output voltage
CAL VLT
A, B, C
Actual voltage
Calibrated measured voltage at external
sense point
CAL CUR A, B, C
Actual current
Calibrate measured current
CAL PWR A, B, C
Actual power
Calibrate measured power.
CLK
INT, EXT
Clock source
CRL
A, B, C
0 to maximum current per phase
Current limit in amps
DLY
0.000 to 9999
Delay in seconds used as a seconds
ramp parameter
DRP
A, B, C
1 through 5
Number of Drop cycles
FRQ
45.00 to 5000
Frequency in hertz
PHZ
A, B, C
0 to 999.0
Phase angle in degrees.
PRG
0 through 15
Load register with preceding data
REC
0 through 15
Recall register or specify link register if it
is preceded by program argument
followed by PRG and register number.
REG
0 through 15
Register load
RNG
A, B, C
0.0 to 270 or other optional range
value
Amplitude range and limit value in volts
SNC
INT,EXT
Synchronize
SRQ
0, 1 or 2
Service Request disable, enable or at
completion of program and
measurements.
STP
From parameter minimum to
maximum value
Define step size in ramp.
TLK
Any header
Set up to talk argument value or
measured value when addressed to talk
TRG
Execute (Trigger) set-up parameters on
GPIB "GET" message
VAL
From parameter minimum to
maximum value
Final ramp or step value in volts, hertz,
amps, degrees, sine wave or square
wave.
WVF A,
B,
C SNW,SQW
Waveform
OPN
Open output relays
CLS
Close
output
relays
VLT
A, B, C
Used with TLK to request measurement
f
Summary of Contents for 2750L-P Series
Page 119: ...INSTRUCTIONAL MANUAL 2750L P 4500L P 6000L P August 2001 Rev K 115 Figure 6 1 MODULE LOCATION...
Page 138: ...INSTRUCTIONAL MANUAL 2750L P 4500L P 6000L P August 2001 Rev K 134 Figure 14 EMERGENCY VOLTAGE...
Page 148: ...INSTRUCTIONAL MANUAL 2750L P 4500L P 6000L P August 2001 Rev K 144 FIGURE 2...