INSTRUCTIONAL MANUAL
2750L-P/4500L-P/6000L-P
August, 2001
Rev. K
-35-
NO SCREEN
NAME
EXTENSIONS
ARGUMENT
ACTION TAKEN
16
CFG
A(LSN)
0-30
Sets the IEEE-488 (GPIB) Listen Address
B(CFG) *28
Defines the features enabled for Power Source
compatibility.
C(PHZ) *120
Defines the phase C initial value for power
system configuration.
17
ALM
A(RNG)
0
Code that defines the default voltage range.
B(LLM)
*135
Defines the upper limit of the lower voltage
range
C(HLM) *270
Defines the upper limit of the higher voltage
range.
18
FLM
A(FRQ)
60
Defines the default frequency.
B(LLM)
*45
Defines the low frequency limit.
C(HLM) *5000
Defines
the high frequency limit.
19 CLM A(RNG) Max
Current
Defines
the maximum current limit value.
B(PRS) *0
Defines the decimal point location for measured
power.
C(CRS) *2
Defines the decimal point location for measured
current.
29
INI
A(AMP)
0-5
Defines default voltage.
C(CRL)
0 - Max Current
Defines the default Current Limit.
*NOT USER PROGRAMMABLE. THE VALUES SHOWN ARE FOR A STANDARD 3-PHASE SYSTEM.
Table 3-8
CONFIGURATION SCREENS
3.5.3
TO PROGRAM OUTPUT VOLTAGE AMPLITUDE (AMP=5)
NOTE
The external sense lines must be connected to J6 on the rear panel of the
AC Power System. If they are not properly connected an AMP FAULT
message will result when the output relay is closed. Refer to Figure 2-3.
The output voltage Amplitude may be programmed independently or simultaneously for each phase.
Select the Amplitude (AMP) screen by entering keystrokes:
5
ENT