Defrosting
When this symbol is lit, the outdoor unit is in defrosting mode. This
is an automatic process to remove the ice from the evaporator. It
takes about 17 minutes and the heat pump will resume working
afterwards. Depending on the ambient temperature and humidity this could
occur several times.
Process of defrosting
:
Water quality requirements
PH Value
6.5 – 8.0
Electrical Conductivity
< 200 µV/cm (25°C)
Total Hardness
< 50 ppm
Sulfone Ion
No
Chloride Ion
< 50 ppm
Ammonia Ion
No
Sulphate Ion
< 50 ppm
Silicon
< 30 ppm
Iron
< 0.3 ppm
Sodium
No
Calcium Ion
< 50 ppm