Calix ODC-80 Installation Guide
101
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2001-2003 Calix. All Rights Reserved.
Appendix: Specifications
ODC-80 cabinet specifications
Wired Capacity
Copper: up to 1920 lines
Fiber: up to 1920 lines
Any copper/fiber combination up to 1920 lines
Dimensions
86"W X 35"D X 72"H
Weight
2,300 lbs.
(Equipped with Dynasty batteries: 3,900 lbs.)
Environmental
Ambient temperature: -40 C to +52 C (per GR-487)
Cooling
Integrated air-to-air cooling system with DC fans
Power
Power feed - 220-240 VAC single phase
60 Amp service with UL listed service disconnect
Redundant AC feeds to rectifier
Redundant DC feeds to Calix C7 shelf
Low voltage DC disconnect
High power AC surge protection (Joslyn)
Alarms
Calix C7 Fuse Fail A+B
All doors
Over temperature
Rectifier Major
Rectifier Minor
AC Fail
AUX/GMT Fuse Fail
Battery Breaker Fail
Low voltage Disconnect
Mounting Options
Pad
Summary of Contents for ODC-10
Page 1: ...Calix ODC 80 Installation Guide July 2003 Part 220 00029 Rev 11...
Page 2: ......
Page 6: ......
Page 7: ...1 Chapter Before You Begin Installing the ODC 80...
Page 8: ......
Page 23: ...2 Chapter Placing the ODC 80 on a Pad...
Page 24: ......
Page 30: ......
Page 31: ...3 Chapter Installing Power Subscriber Cables and Equipment...
Page 32: ......
Page 74: ......
Page 75: ...4 Chapter Maintaining and Troubleshooting the ODC 80...
Page 76: ......
Page 80: ......
Page 92: ......
Page 103: ...5 Chapter Reference...
Page 104: ......
Page 106: ......