Cabinet over temperature alarm
Alarm output
When the alarm occurs, the following message displays:
TID-000 01-09-10 11-15-00
** 001 REPT ALM ENV
"N2-1:MJ,HITEMP,SA,9-10,11-15-00,NEND;"
Clearing output
You will see this message once the alarm has been cleared from the system:
TID-000 01-09-10 11-55-00
A 001 REPT EVT ENV
"N2-1:HITEMP,CL,9-10,11-55-00;"
Description
Severity
The over temperature (HITEMP) alarm indicates that the outdoor
cabinet has exceeded the allowable temperature for the Calix C7
equipment to operate. The outdoor cabinet will generate an over
temperature alarm at 158F (70C).
There are two heat exchangers located in the sidewalls of the main
equipment area: one internal and one external. The internal heat
exchanger fans activate at 77F (25C), and the external heat exchanger fans
activate at 86F (30C).
Major