Replacing Batteries
If a battery or string of batteries fails, becomes damaged, or wears out its life, you can replace
the battery or string as described below. Replacing batteries does not impact cabinet service,
provided that an AC power failure does not occur during the replacement process. Calix
recommends connecting an external generator to the cabinet while performing battery
maintenance to ensure service continuity in the event of an AC outage.
WARNING!
Electrical hazard. Batteries contain a stored charge. Only a
qualified technician should perform this procedure.
CAUTION!
Electrical, chemical, fire, and heat hazard. Handle batteries with
care to avoid personal injury or damage to the equipment.
ALERT!
To ensure service continuity in the event of an AC outage, connect
an external generator to the cabinet while performing battery maintenance.
To replace batteries
1.
At the DC distribution panel, switch the breaker(s) for the battery string(s) to replace to
OFF
.
2.
Remove the front and rear battery compartment doors. See
Operating Cabinet Doors
(on
) for instructions.
3.
In the battery compartment, remove the front seismic protection brackets from around
the batteries, if present.
4.
Identify the #10 AWG battery power cables for the string(s) to replace. Disconnect the
identified cables (Anderson connectors) from the power supply leads.
5.
Remove the red and black battery power cables from the terminals at each end of the
string.
6.
Remove the jumper straps from between the terminals of batteries in the string.
7.
Remove the batteries from the battery compartment.
8.
Install the new batteries. See Installing Batteries for instructions.
9.
When finished, replace the front seismic protection brackets, if present.
10.
Replace the battery compartment doors and switch the battery breaker(s) to
ON
.