background image

Page 6

SD092750 ISSUE 34

3. Plumbing

a) The Calorex Variheat Heat Pump must be

connected after the filter in the return pipe to the
pool. If an existing heater is being retained, then
the Calorex unit should be connected between
the filter and the other heater, see figure 6.

b) Calorex heat pumps have water inlet/oulet

connections  as  follows:
Models 550,800,1200 1½” BSP parallel, female.
Models 1400, 1800 & 4000 1½” BSP parallel,
male.

c) Suitable breakable couplings should be

installed local to heat pump.

d) If heat pump installed at lower level than pool

water then isolation valves should be fitted.

e) Drain valve or plug should be fitted to lower to

facilitate completedrain down in winter period.

f) Connections on all models from 550 to 1200 are

by parallel male fittings sealed by 'O' ring or
silicone mastic these should be 

hand tightened

only

, otherwise damage may result to the

threads.

Note:

 Do not route pipes across service panels or

Air In/Outlet

g) The heat exchanger in the Heat Pump will, on

small pools, take the full flow rate of the
recirculating system (see Figure 6). On larger
pools a by-pass or separate auxiliary pump
may be necessary. (bypass 1½ hp or larger
water pumps) see Figures 7 and 8.

h) The condensate drain at the base of the unit

collects the condensation from the evaporator
fins. It is therefore necessary to ensure
that the Calorex is placed on a level plinth so
that the condensate water can run away and not
overflow the edges of the drip-tray inside the
machine.
Models 550,800,1200
drain connection to waste via 22mm push fit
domestic waste  system.
Models 1400, 1800 and 4000
drain connection to waste via ¾2 & 1½” BSPM
stubs respectively.

N.B Hose must be a watertight fit.

i) When the pipework installation is complete the

pool pump should be switched on and the
system tested for leaks. Also check the filter
gauge to see that there is not an excessive
increase in back pressure. If everything is then
working normally  the water circulating  system is
ready to use.

j) Water circuit to and from unit to be capable of
maintaining within specified limits the rate of flow
required by heat pump (see data sheet).

k) All pipework must be adequately supported with

allowance for expansion/  contraction especially with
plastic  pipework.

I) It is recommended that when installing water system

the last connections to be made in the system

   should be the breakable connections to avoid any

stresses on to the unit connections.

m)To ensure efficient operation of the Heat Pump, an

adequate constant flow of water is required through
the condenser.
This is normally achieved by ensuring that the filter
pump is always operating at the same time as the
Heat Pump but this requires consumption of electricity
which would not normally be used during the filter ‘off
cycle’ period.

To reduce energy consumption the installation of a two
speed or small auxillary water pump (by-passing the
filter) should be considered. This method should only
be used on heavily used pools (4 hours turnover or
less to reduce the risk of overheating due to main
pump heat  input.

The circuit can be incorporated in the initial installation
or added to an existing standard circuit.

IMPORTANT

1) The Calorex unit must never be connected in such a

way that the Heat Pump can be switched on without
adequate water flow through the condenser.
Integral interlock terminals provided on all models
(see figure 9).

2)  All Pool Purifying Devices and Chemical Injection

Systems to be fitted down stream of heat pump with a
non return valve to prevent concentrated chemicals
back feeding into the heat exchanger. The practice of
dosing chemicals direct into  Skimmer Basket, which
results in concentrated corrosive liquids passing over
vulnerable metal components must  not be allowed.

3) Water quality must be maintained not only related to

solids, etc, but also pH between 7,4 ±0,4 and, if pool
water is saline at maximum concentration of 6% wt/wt.

4) Maximum pressure of water in heat pump circuit id

3kg/cm².
(140psi) 1400, 1800,4000 models.

Summary of Contents for AW1400

Page 1: ...General Introduction 2 Installation 3 1 Siting 3 2 Ducting 3 3 Plumbing 6 4 0 Electrolytic corrosion in swimming pools 9 4 1 Electrical 10 Controls and Indication Lamps 20 Variheat Commissioning 21 H...

Page 2: ......

Page 3: ......

Page 4: ...ng rubber or canvas to eliminate transmission of vibration down the duct 5 Before any discharge ducting is attached remove plate if fitted from machine outlet or fan grille 6 After completion of insta...

Page 5: ......

Page 6: ......

Page 7: ...If everything is then working normally the water circulating system is ready to use j Water circuit to and from unit to be capable of maintaining within specified limits the rate of flow required by...

Page 8: ......

Page 9: ......

Page 10: ......

Page 11: ...360V 440V Single Phase Machines 60Hz 187 253 Three Phase machines 60Hz 187 253 Cycle Frequency 50Hz 47 5Hz 52 5Hz Cycle Frequency 60Hz 57 0Hz 63 0Hz INTERLOCK All units have interlock circuits incorpo...

Page 12: ...t Soft Start Remove Front Service Panel turn fasteners 14 1800 Mains Terminal and Earthing Point also External Interlock see Fig 9 Mains Supply In 4000 Mains Terminal and Earthing Point also External...

Page 13: ...LP SWITCH POOL STAT POOL PUMP STARTER OR FLOW SWITCH SOLENOID VALVE FAN CAP HUMIDISTAT CONTACTOR O LOAD SOFT START IF FITTED L1 L2 L3 11 14 CONTROL FUSES PHASE ROTATION RELAY N O CLOSES ON WATER TEMP...

Page 14: ...ST STAT DEFROST LIGHT HUMIDISTAT MCB ALARM COMPRESSOR FAN MCB ALARM NC FAULT LIGHT L3 L2 L1 INTERLOCK TERMINALS SOLENOID VALVE POOL STAT SOLENOID COIL D 1 3 4 2 COIL C VALVE RUN STANDBY SWITCH STANDBY...

Page 15: ...RAM ABOVE CONDITIONS APPLY 3 N O L C C H COMPRESSOR C S R CONTACTOR DELAY TIMER DEFROST LAMP POOL STAT HUMIDISTAT SOLENOID COIL INTER LOCK FAULT LAMP FUSE FAN FAN CAP MAINS LAMP N A B COM 7 4 N O RELA...

Page 16: ...2 13 14 15 16 FUSE 3A 3A 16A 19 7A MACHINE OVERLOAD SETTING 1400 1800 COMPRESSOR FAN FAN BRHF 7 6A 9 2A 1 1A 1 1A 1 2A 1 2A SOFT START IF FITTED C B A D FUSE D159651 N O 11 COM L3 L2 L1 PHASE ROTATION...

Page 17: ...CAP HUMIDISTAT CONTROL FUSE FAN FUSE L1 FUSES CONTACTORS OVER LOADS FAN COMPRESSOR R S C HEATER DELAY TIMER DEFROST STAT DEFROST LIGHT HP SWITCH LP SWITCH FAN AUX N O COMPRESSOR OVERLOAD CONTROL FUSES...

Page 18: ...B MCB SOFT START IF FITTED 14 11 L3 L2 L1 MOTOR PROTECTOR T1 T2 CONTROL MCB PHASE ROTATION LP SWITCH BREAKS TO H ON PRESSURE FALLING HP SWITCH BREAKS TO L ON PRESSURE RISING L H C N O N C COM L H C N...

Page 19: ...DEFROST STAT THERMAL O LOAD FAULT LIGHT IF INTERLOCK TERMINALS FUSES CONTACTORS O LOADS FAN COMPRESSOR HEATER S POOL STAT COIL C 1 2 LP SWITCH BREAKS TO H ON PRESSURE FALLING FAULT LIGHT COMPRESSOR MA...

Page 20: ...N C 2 N C 6 N C 5 5 5 5 3 3 3 3 1 1 1 1 14 SOFT START IF FITTED D321050 R S C TIMER DELAY DEFROST STAT HUMIDISTAT THERMAL O LOAD FAULT LIGHT IF DEFROST LIGHT INTERLOCK TERMINALS FUSES CONTACTORS O LO...

Page 21: ......

Page 22: ...minute delay NOTE Machine will only operate correctly when all service panels are in place 3 Tum or switch off water circuit interlock should operate unit compressor stops Fault lamp ON 4 Restore wat...

Page 23: ...service calorex com User Check List MAINS RED ON OFF Check electrical supply FAULT AMBER OFF external fuse isolator etc DEFROST WHITE OFF Check standby sitch ON 4000 only MAINS RED ON Check humidistat...

Page 24: ...FUSE STD 1 ph N amps 15 25 35 N A N A N A MAX SUPPLY FUSE F 1 ph N amps 20 32 35 N A N A N A MAX SUPPLY FUSE STD 3 ph N amps 10 13 20 15 16 40 MAX SUPPLY FUSE F 3 ph N amps 16 16 20 15 16 40 STARTING...

Page 25: ...amps N A N A N A N A N A 40 STARTING CURRENT STD MODEL 1ph amps 60 82 140 118 147 N A STARTING CURRENT SOFT START S MODEL 1ph amps 28 30 36 35 38 N A STARTING CURRENT STD MODEL 3ph 230V amps N A N A N...

Page 26: ...l 1800 VH 5 75 10 4 14 Model 4000 VH 2 units required 12 1 22 30 Electrical Input kW 0 36 0 72 0 72 Supply Fuse 1 Amps Power supplied from VH unit Fan Amps Amps 1 5 2 x 1 5 2 x 1 5 Air Flow m h 2000 3...

Page 27: ...51 MAINS INLET FRONT SERVICE PANEL 50 940 268 75 720 OPTIONAL AIR OUTLET REAR VIEW AIR INLET AIR SAMPLING POINT 185 265 660 355 660 AIR OUTLET SERVICE PANEL FRONT SERVICE PANEL TOP VIEW 150 WATER OUT...

Page 28: ...also available OPTIONAL AIR OUTLET REAR VIEW 1030 730 496 188 MAINS INLET 580 565 L H SIDE 80 1060 295 496 1250 185 530 630 R H SIDE 161 40 50 LIQUID DISCHARGE RCU STUBS If fitted AIR OUTLET L H SERV...

Page 29: ......

Page 30: ...2 1 2 15m Condenser Rows 4 3 5 1 2 1 2 30m Fins per inch 10 10 10 1200 1 2 1 2 15m 5 8 1 2 30m Fuse Size Amps 5 7 7 FLA amps 1 3 2 6 2 6 1400 5 8 5 8 15m Suction Size 1 2 5 8 3 4 5 8 5 8 30m Liquid Si...

Page 31: ......

Page 32: ......

Page 33: ......

Page 34: ......

Page 35: ...TER ACCESS FILTER ACCESS When the side access air filter kit is fitted it is necessary to leave space at either one or both sides of the machine to allow for the access to the filters Remove filter ac...

Page 36: ...ails of extended warranty and maintenance packages available to United Kingdom customers please call the service number below IF IN ANY DOUBT PLEASE ASK Note The Reply Paid Warranty Registration Card...

Page 37: ...n required Date Test Result Comments Testing of Automatic Leak Detection System if fitted Engineer Reason for removal What done with recovered refrigerant General Information Refrigerant Additions Eng...

Page 38: ...capacitor tolerances where fitted 5 Check condition of all heat exchangers evaporators 6 Check refrigeration system parameters 7 Check operation of control valves 8 Check for water leaks 9 Check drip...

Reviews: