Installation Manual
AW629/829AL
Page 22
R
In the event that the heat pump appears to have a water leak but this water
is not overflowing from the drip tray, carefully inspect all the joints within
the heat pump heat exchanger assembly for pool water leaks and repair as
necessary.
General rule of thumb check
list
After switching on, the heat pump will take approx six minutes to start.
This is due to inbuilt time delays within the heat pump that protect the
compressor from short-cycling.
Air leaving the heat pump should be 8 to 10 °C colder than its entering
temperature.
Water leaving the heat pump will typically be no more than 3 °C warmer
than its entering temperature.
On warm days a steady trickle of condensate water should discharge from
the condensate drain.