28
1002595 ISSUE 5 M172 VARIHEAT
VARIHEAT AA SYSTEM OWNER INSTALLATION MANUAL
BMS SETTINGS
Press this button on the Advanced Settings menu.
This screen contains settings related to BMS connectivity when using Modbus/
RTU and BACnet MS/TP through the spare RS485 port. The factory default
settings are shown. If connecting using BACnet/IP, see the PLC Ethernet
Settings screen on page 30..
Slave Address. Can be set from 0 to 255.
Baud Rate. Can be set from 0 to 5, corresponding to:
0
9600
1
19200
2
38400
3
57600
4
76800
5
115200
Protocol Used. Can be set from 2 to 4, corresponding to:
2
uNET
3
Modbus/RTU
4
BACnet MS/TP
Data Bit. Always set to 8. Included for information only, to configure own
software if needed.
Parity Bit. Can be set from 0 to 2, corresponding to:
0
Null
1
Odd
2
Even
Stop Bit. Can be set from 1 to 2.
BACnet/IP Port – can be set from 0 to 65535. 0 corresponds to the default port
47808. 65535 corresponds to BACnet stack running only on PLC side.
After changing any of the above settings, restart the PLC/Variheat, by
cycling the power supply, to save and apply the new settings.
For Modbus Variable list and BACnet Object list please consult the Dantherm
Group.
Arrow icon
Return to
User Settings
Home icon
Return to
Home screen
Summary of Contents for Variheat AA1200
Page 2: ......
Page 69: ...69 1002595 ISSUE 5 M172 VARIHEAT...
Page 70: ...70 1002595 ISSUE 5 M172 VARIHEAT...