55
1002595 ISSUE 5 M172 VARIHEAT
5.1 LPHW HEATING DATA - VARIHEAT WITH STANDARD AIR HEATER
flow °C
80
70
60
50
45
AA600
standard air heating capacity
kW
11.0
8.8
6.6
4.4
3.3
recommended boiler capacity
kW
11.0
8.8
6.6
4.4
3.3
LPHW flow rate
L/min
10
10
10
10
10
return temperature
°C
64.2
57.4
50.5
43.7
40.3
flow °C
80
70
60
50
45
AA900
standard air heating capacity
kW
13.5
10.8
8.1
5.4
4.1
recommended boiler capacity
kW
13.5
10.8
8.1
5.4
4.1
LPHW flow rate
L/min
10
10
10
10
10
return temperature
°C
60.7
54.5
48.4
42.3
39.2
flow °C
80
70
60
50
45
AA1200
standard air heating capacity
kW
24.0
19.2
14.4
9.6
7.2
recommended boiler capacity
kW
24.0
19.2
14.4
9.6
7.2
LPHW flow rate
L/min
22
22
22
22
22
return temperature
°C
64.4
57.5
50.6
43.7
40.3
flow °C
80
70
60
50
45
AA1500
standard air heating capacity
kW
28.0
22.4
16.8
11.2
8.4
recommended boiler capacity
kW
28.0
22.4
16.8
11.2
8.4
LPHW flow rate
L/min
22
22
22
22
22
return temperature
°C
61.8
55.4
49.1
42.7
39.5
°C
65
60
55
50
45
AA600
upgraded air heating capacity
kW
12.8
11.0
9.2
7.3
5.5
recommended boiler capacity
kW
12.8
11.0
9.2
7.3
5.5
LPHW flow rate
L/min
14
14
14
14
14
LPHW return temperature
°C
51.9
48.7
45.6
42.5
39.4
°C
65
60
55
50
45
AA900
upgraded air heating capacity
kW
15.8
13.5
11.3
9.0
6.8
recommended boiler capacity
kW
15.8
13.5
11.3
9.0
6.8
LPHW flow rate
L/min
14
14
14
14
14
LPHW return temperature
°C
48.9
46.2
43.5
40.8
38.1
°C
65
60
55
50
45
AA1200
upgraded air heating capacity
kW
28.0
24.0
20.0
16.0
12.0
recommended boiler capacity
kW
28.0
24.0
20.0
16.0
12.0
LPHW flow rate
L/min
44
44
44
44
44
LPHW return temperature
°C
55.9
52.2
48.5
44.8
41.1
°C
65
60
55
50
45
AA1500
upgraded air heating capacity
kW
32.7
28.0
23.3
18.7
14.0
recommended boiler capacity
kW
32.7
28.0
23.3
18.7
14.0
LPHW flow rate
L/min
44
44
44
44
44
LPHW return temperature
°C
54.4
50.9
47.4
43.9
40.4
Data based on air 30°C, pool water 28°C
5.2 LPHW HEATING DATA - VARIHEAT WITH UPGRADED AIR HEATER
(WHERE MODEL NUMBER INEC LPHW)