35
1002595 ISSUE 5 M172 VARIHEAT
Optional fresh air
module wi
th
two spigots
(225mm diameter)
or Negative pressure module
wi
th
one spigot
(157mm diameter)
Return air
from
pool hall
Service panel
Damper
Spigot
Service panel
Air filter access panel
Service access area (minimum)
Required for all service panels
800
Vertical, upflow range
Supply air to pool hall
Service panel
Service panel
Damper
Spigot
Service panel
Air filter access panel
Vertical, downflow range
Supply air to pool hall
Horizontal range
Service panel
Damper
Service panel
Air filter access panel
Spigot
Service panel
Supply air
to pool hall
Removable display
panel gives access
to electric box
Optional resistance heater
module in this position only
Optional fresh air
module wi
th
two spigots
(225mm diameter)
or Negative pressure module
wi
th
one spigot
(157mm diameter)
Optional resistance heater
module in this position only
Touchscreen
user interface
Return air
from pool hall
Return air
from
pool hall
Optional resistance heater
module in this position only
Service panel
Optional fresh air
module wi
th
two spigots
(225mm diameter)
or Negative pressure module
wi
th
one spigot
(157mm diameter)
All ambient air ducting should be suitably insulated if plant room temperatures are significantly different from ambient, particularly where the plant room is at pool
conditions. Spring return dampers are recommend for exhaust and fresh air ductwork in installations with sub zero ambient temperatures, in case of power failure.
Important
AA600, 900 and 1200 models are fitted with constant flow fans and self-regulate to deliver the optimum airflow, compensating for pressure differentials in the
system. AA1500 models are fitted with a variable speed, so the fan speed should be commissioned to ensure the correct volume (with dry coils, clean air filter and
all panels fitted). See data sheet for pressures available.