1002594 ISSUE 1 M172 VARIHEAT
VARIHEAT AW SYSTEM OWNER INSTALLATION MANUAL
Press the left side of
the colon to change the
hour setting.
Press the right side of
the colon to change the
minute setting.
This screen can also be accessed from the first Home screen if the User Security
settings are set to allow access.
When one of the time settings is touched, the keypad appears to allow the
parameter to be changed. Any time with a white background can be changed.
There are two periods per day, A and B. Days can be set individually, or copied
to the whole week. If A and B periods overlap, priority is given the Occupied
period. If one Occupied period is required, period B can be disabled.
The current Occupied air temperature and the Unoccupied air temperature
settings are shown. The Unoccupied setting is set as the difference between
the two, which can be changed. In the example above, the Occupied air
temperature setting is 28.0°C and the Unoccupied air temperature setting is
4.5°C below that, 23.5°C. The minimum night set back temperature controlled
by the Variheat is 22°C. This means that the greatest difference allowed is 6°C.
Press the Home button to return to the User Settings screen.
TIME CLOCK
Press this button on the Settings menu.
Home icon
Return to
Home screen
If a second occupied period is
required enable this button.
Times in the second period
can be entered in B.
The times for the rest of
the week can be copied by
pressing this button.