1002594 ISSUE 1 M172 VARIHEAT
BMS SETTINGS
Press this button on the Advanced Settings menu.
This screen contains settings related to BMS connectivity when using Modbus/
RTU and BACnet MS/TP through the spare RS485 port. The factory default
settings are shown. If connecting using BACnet/IP, see the PLC Ethernet
Settings screen on page 32.
Slave Address. Can be set from 0 to 255.
Baud Rate. Can be set from 0 to 5, corresponding to:
0
9600
1
19200
2
38400
3
57600
4
76800
5
115200
Protocol Used. Can be set from 2 to 4, corresponding to:
2
uNET
3
Modbus/RTU
4
BACnet MS/TP
Data Bit. Always set to 8. Included for information only, to configure own
software if needed.
Parity Bit. Can be set from 0 to 2, corresponding to:
0
Null
1
Odd
2
Even
Stop Bit. Can be set from 1 to 2.
BACnet/IP Port – can be set from 0 to 65535. 0 corresponds to the default port
47808. 65535 corresponds to BACnet stack running only on PLC side.
After changing any of the above settings, restart the PLC/Variheat, by
cycling the power supply, to save and apply the new settings.
For Modbus Variable list and BACnet Object list please consult Calorex.