1002594 ISSUE 1 M172 VARIHEAT
If unit is located in a plant room at pool hall air temperatures, any ambient air ducting must be heavily insulated.
Recommend fresh air/exhaust spring return dampers to be fitted to ductwork for sub zero ambient
applications in case of power failure.
IMPORTANT - 600 and 900 models are fitted with constant flow fans and deliver the
optimum airflow, self compensating for pressure differentials in the system.
On 1200 and 1500 models ensure duct work pressure drop does not exceed resistance
given in data sheet. Damper plates fitted on side of fan CAN be removed if ducting is fitted
but fan amps MUST be verified to be as per data sheet fan amps with dry coils, clean air
filter and all panels fitted.
Optional fresh air
module with two spigots
(225mm diameter)
or Negative pressure box
with one spigot
(157mm diameter)
Return air
from
pool hall
Service panel
Damper
Spigot
Service panel
Service
panel
Air filter access panel
Service access area (minimum)
800
Required for all service panels
Vertical, upflow range
Supply air to pool hall
Service panel
Service panel
Damper
Spigot
Service panel
Air filter access panel
Vertical, downflow range
Supply air to pool hall
Horizontal range
Service panel
Damper
Service panel
Air filter access panel
Spigot
Service panel
Electric box assembly
Supply air
to pool hall
Remov
able display panel
giv
es access to electric box
Optional resistance heater
box in this position only
Optional fresh air
module with two spigots
(225mm diameter)
or Negative pressure box
with one spigot
(157mm diameter)
Optional resistance heater
box in this position only
Optional fresh air
module with two spigots
(225mm diameter)
or Negative pressure box
with one spigot
(157mm diameter)
Touchscreen
user interface
Return air
from pool hall
Return air
from pool hall
Optional resistance heater
box in this position only
All ambient air ducting should be suitably insulated if plant room temperatures are significantly different from ambient, particularly where the plant room is at pool
conditions. Spring return dampers are recommend for exhaust and fresh air ductwork in installations with sub zero ambient temperatures, in case of power failure.
Important
AW600, 900 and 1200 models are fitted with constant flow fans and self-regulate to deliver the optimum airflow, compensating for pressure differentials in the
system. AW1500 models are fitted with a variable speed, so the fan speed should be commissioned to ensure the correct volume (with dry coils, clean air filter and
all panels fitted). See data sheet for pressures available.