35
Figure 6 Rolling sphere method to determine the lightning protection zones
Assess locations on masts,
towers and buildings to
determine if the location is
in Zone A or Zone B:
Zone A: In this zone a
direct lightning strike is
possible. Do not mount
equipment in this zone.
Zone B: In this zone,
direct EMD (lightning)
effects are still possible,
but mounting in this
zone significantly
reduces the possibility
of a direct strike. Mount
equipment in this zone.
Warning
Do not mount equipment in Zone A which can put the equipment, structures and life at risk.