I nst alling t he I F and ground cables
Chapt er 5: I nst allat ion
5- 54
phn- 2513_004v000 ( Oct 2012)
Making an IF cable ground point
Perform this task to connect the screen of the IF cable to the metal of the supporting
structure using a cable grounding kit.
The cable grounding kit for 1/4” and 3/8” cable (
) contains the following
components:
•
1 x grounding cable with grounding 2 hole lug fitted (M10)
•
1 x self Amalgamating tape
•
1 x PVC tape
•
3 x tie wraps
•
2 x bolt, washer and nut
Install ground cables installed without drip loops and pointing down towards the ground,
otherwise they may not be effective.
To ground the IF cable to a metal structure using the Cambium grounding kit (part
number 01010419001), proceed as follows:
1
Remove 60 mm (2.5 inches) of the IF cable outer jacket: