Cambridge Air Solutions
34
S-Series Technical Manual
INSTALLATION INSTRUCTIONS
VERTICAL S-SERIES STRUCTURAL FILTER SECTION
The Structural Filter Section is designed to be used with any S-Series vertical installation (indoor/outdoor, up/down
blast). It designed to be load bearing and can support the weight of the unit with all necessary additional ductwork. It
is designed with a set of doors on both sides to ensure that it can never be installed backwards. It can either be hung
from the ceiling or mounted on top of the 4’ adjustable mounting stand or structural inlet elbow with 4 accessory
mounting brackets. It is capable of using permanent, disposable, or MERV-13 filters. All Structural Filter Sections
are insulated and double skinned to help mitigate con-densation, noise, and thermal losses.
Model
Weight
A
B
C
S400/S800
150 lbs.
30 3/8”
25 3/8”
25 3/8”
S950/S1200/S1600
175 lbs.
25 3/8”
28”
42”
S1850/S2200/S3200
235 lbs.
30 3/8”
37 1/8”
47”
Model
Filters
Quantity
Dimensions
S400/S800
2
20” x 25” x 2”
S950/S1200/S1600
4
20” x 25” x 2”
S1850/S2200/S3200
12
16” x 25” x 2”
Indoor Up Blast
Outdoor Up Blast
Structural
Airflow
brackets (Qty 4)
Indoor Down Blast
Structural
C
B
A
Airflow