S-Series Technical Manual
37
Cambridge Air Solutions
INSTALLATION INSTRUCTIONS
S-SERIES 24”, 38”, & 50” WALL SLEEVES
The S-Series wall sleeves (24”, 38”, and 50”) are suitable for discharge duct work for either vertical or horizontal
configurations. They are designed to be attached at its inlet side by a retaining clip and two side brackets. The
discharge end is designed to hold either additional accessories by the same method (a retaining clip and two side
brackets) or a set of directional elbows and discharge collar. All wall sleeves are insulated to help mitigate noise and
thermal losses.
Airflow
50” wall sleeve
38” wall sleeve
Horizontal Mounted
24” wall sleeve
plates (Qty 2)
Retaining clip
Airflow
C
B
A
Heater Size
Sleeve Weight
A
B
C
S400/S800
24”
35 lbs.
13”
25 3/8”
24”
38”
50 lbs.
13”
25 3/8”
38”
50”
65 lbs.
13”
25 3/8”
50”
S950/S1200/S1600
24”
50 lbs.
15”
42”
24”
38”
75 lbs.
15”
42”
38”
50”
95 lbs.
15”
42”
50”
S1850/S2200/S3200
24”
60 lbs.
24 1/8”
47”
24”
38”
90 lbs.
24 1/8”
47”
38”
50”
115 lbs.
24 1/8”
47”
50”