CV-7600 SERIES -BLE  BLUETOOTH CARD READER

INSTALLATION INSTRUCTIONS

Notes: 
a) 

Single Line LED:

This is the standard operating mode and does not make use of 
the Orange conductor. The LED is Red when the reader is idle and 
flashes when a card is presented. The LED turns Green when the 
Brown conductor is pulled low by the access control panel.

b) 

Dual Line LED:

This mode makes use of both the Brown and Orange 
conductors. The Brown conductor controls the Red LED and 
the Orange conductor controls the Green LED. LED states are 
determined by the access control system option and capability.

WIEGAND

Wire Color

Function

RED

DC  (8 -14 VDC)

BLACK

Ground

GREEN

DATA 0

WHITE

DATA 1

BROWN

RED LED (a)

ORANGE

GREEN LED (b)

YELLOW

NOT USED

BLUE

BEEPER

VIOLET

READ MODE (c)

DRAIN

SHIELD GROUND

c) 

Read Mode:

In regards to contactless smart card credentials, the reader will 
only read and output the credential's Card Serial Number (CSN) 
when the Violet conductor is pulled low (connected to ground). 
Otherwise, the reader will only read and output the credential's 
programmed Sector data.

Unused conductors should be trimmed, isolated and taped 
back to prevent unintended current flows. Apply positive 
voltage only to the Red DC Conductor.

a) 

Cable Requirements:

24 AWG minimum, multi-conductor stranded with an overall 
foil shield, for example Belden 9535 or similar, supporting the 
five conductors comprising the physical layer of the Wiegand 
interface (power, ground, data 0, data 1, and/or beeper and LED).

Alternatively, Belden 9539 or similar, for all reader functions. 
Contact your access control system manufacturer for their 
specific requirements. Per the SIA’s Wiegand specification, 
maximum cable length is 500 feet (152 m).

b) 

Output Formats:

Wiegand (industry standard 26-bit Wiegand and custom 
Wiegand formats).

c) 

Grounding:

Shield (drain) continuity must run from the reader to the access 
panel. Shield (drain) and reader ground must be tied together at 
the access panel and connect to an earth ground at one point.

d) 

Power:

Reader may be powered by the access control panel. A linear 
power supply is recommended for best operation. 8 to 14 VDC, 
12 VDC at the reader is best.

e) 

Read Mode:

For sector data reads, do not connect the Violet conductor 
(leave it high). For CSN reads, pull the Violet conductor low 
(connect the Violet conductor to ground).

Reader Model

Read Range

CV-7600

1 foot

CV-7605

5 feet

CV-7615

15 feet

CV-7630

30 feet

CREDENTIAL

Model

Description

CV-MBT

BLE Mobile Credentials

CV-MCS

Mobile Clam Shell Cards

CV-MKT

Mobile Key Fob, 2K memory

Reviews: