background image

Page 7 of 28

CX-33 Advanced Logic Relay Installation Instructions

Section 3L

Mag Lock with N.O. Fire Alarm  
(Mode 11)

Commonly seen in hospital corridors, this version of a 
switching network (make/break relay) is specifically designed 
for doors with mag locks.

A wall switch signals the relay, which unlocks, and opens the 
door for an adjustable time. Utilizing the door position switch, 
the CX-33 will not re-apply power to the magnetic lock until 
the door is fully closed. The relay also provides for a normally 
open Fire Alarm input, which when activated, unlocks the 
door and disables the wall switch inputs.

Refer to 

Diagram 11

, (Page 22) for the following 

connections:

Momentary switches connect to DRY 1 and/or WET terminals. 
Maintained devices connect to DRY 2 input (optional). The N.O. 
Fire Alarm signal is wired to DRY 3 input, and the Door Position 
Switch connects to DRY 4 input. The circuit must be closed 
when the door is closed, and open when the door opens.

The magnetic lock connects to the Common and N.C terminals 
of Relay 1. The door operator connects to the Common and 
N.O. terminals of Relay 2. Relay 3 output is optional.

Once input and output connections are made, program the 
unit according to the General Programming Instructions on 
page 1, and walk-test the installation. Timing adjustments 
may need to be made.

It is NOT recommended to add the “Delay-on-activate”  
(or nuisance delay) feature in this mode!

Once the desired operation is achieved, proceed to Section 
4, Pg 9 for 

System Inspection Instructions

.

Section 3M

Mag Lock with N.C. Fire Alarm  
(Mode 12)

This mode is identical to Mode 11 (Section 3L) except the 
Fire Alarm input is a N.C. circuit (rather than N.O.). See 
previous section for wiring and adjustments, & refer to 

Diagram 12

, (Page 23).

Section 3N

Special Purpose Sequencer  
(Mode 13)

In this mode, Input 1 sequences Relays 1 & 2, Input 2 
sequences Relays 2 & 3. Input 3 sequences Relays  

Section 3K

Low Energy SAM Plus  
(Mode 10)

This mode combines a Low-Energy Secondary Activation 
Module (SAM) with a switching network (aka make/break 
relay). Utilizing a door position switch input, this mode 
enables or disables a door mounted presence sensor. The 
sensor is put into the circuit when a wall switch is pressed 
(a Knowing Act). This allows an object or person in the path 
of the door to be detected. The door will not close until the 
object or person leaves the door swing path. The sensor 
remains in the circuit until the door is closed.

When the door is opened manually, the safety sensor is not  
in the circuit and the door operator functions as a manual 
door closer.

A unique feature of the CX-33 is the automatic reset feature. 
If a switch has been pressed, but the door has not opened 
within 60 seconds (because it is locked, for instance), the unit 
will reset. This will save wear and tear on the lock and operator.

In addition, one input and two relays are provided for the 
switching network function.

Refer to 

Diagram 10

, (Page 21) for the following connections.

SAM Circuit:

Connect the momentary activating switch(es) to DRY 3 input. 
The door mounted sensor connects to DRY 2 input, and the 
magnetic contact switch connects to DRY 4 input. The contact 
switch circuit must be closed when the door is closed, and 
open when the door opens.

 
Relay 3 output is to be connected to the Activate circuit of the 
door operator.

Optional Switching Network:

Wire the activating device(s) to DRY 1 terminals. Wire the 
outputs as shown to Relays 1 & 2.

Once input and output connections are made, program the 
unit according to the General Programming Instructions on 
page 1, and walk-test the installation. Timing adjustments 
may need to be made.

It is NOT recommended to add the “Delay-on-activate”  
(or nuisance delay) feature in this mode!

Once the desired operation is achieved, proceed to Section 4, 
Pg 9 for 

System Inspection Instructions

.

CX-33 Advanced Logic Relay Installation Instructions

Summary of Contents for CX-33

Page 1: ...read the instructions fully and made the required adjustments Mounting The CX 33 should be mounted in a clean dry location out of direct contact with the elements Suitable locations include inside a m...

Page 2: ...contact N O or N C 3 Set Dry Input 3 to activate on normally open or normally closed contact N O or N C 4 Set Dry Input 4 to activate on normally open or normally closed contact N O or N C 5 Set Wet...

Page 3: ...ergy S A M w switching network Mode 10 Proceed to section 3K on Page 7 Mag lock with N O Fire Alarm input Mode 11 Proceed to section 3L on Page 7 Mag lock with N C Fire Alarm input Mode 12 Proceed to...

Page 4: ...tive adjustable timers If the time is set to zero then this feature is disabled Refer to Diagram 3 Page 13 for the following connections Wire the activating device s for Door 1 to DRY 1 terminals Wire...

Page 5: ...nlock and open the door Refer to Diagram 6 Page 17 for the following connections The CX 33 allows for dry and or powered maintained connections to the Access System time clock DRY 1 and or WET inputs...

Page 6: ...s are made program the unit according to the General Programming Instructions on page 1 and walk test the installation Timing adjustments may need to be made It is NOT recommended to add the Delay on...

Page 7: ...1 2 Input 2 sequences Relays 2 3 Input 3 sequences Relays Section 3K Low Energy SAM Plus Mode 10 This mode combines a Low Energy Secondary Activation Module SAM with a switching network aka make break...

Page 8: ...am 7a page 26 for connections The all active switches and Lock down Switch are all normally open switches The RESET switch is normally closed Connect as shown A fail safe electric strike or mag lock s...

Page 9: ...y 320 mA max Inputs 4 x dry contacts and 1 x wet contact 4 5 120 V AC DC Optically isolated non polarity sensitive Response time 0 5 seconds Relay Output 3 x Form C SPDT Relay contact rating 3 amps 24...

Page 10: ...Page 10 of 28...

Page 11: ...Page 11 of 28...

Page 12: ...Page 12 of 28...

Page 13: ...Page 13 of 28...

Page 14: ...Page 14 of 28...

Page 15: ...Activating Switch Door 1 sequences relays 1 to 2 to 3 LED 1 LED 2 LED 3 DISPLAY Relay 1 Relay 2 Relay 3 N C N O COM N C N O COM N C N O COM POWER 12 24V AC DC DRY 1 DRY 2 DRY 3 DRY 4 WET INPUT INPUT I...

Page 16: ...ut 4 fires relay s 2 3 and holds both until input is released 6 Relay 3 can be used for a status indicator 7 Wet I P activates on 4 5V AC DC Older interphone panels may produce a stray voltage when in...

Page 17: ...relay or if available Dry 1 Input LED 1 CX 33 LED 2 LED 3 DISPLAY Relay 1 Relay 2 Relay 3 N C N C N O N O N O N C COM COM COM POWER 12 24V AC DC DRY 1 DRY 2 DRY 3 DRY 4 WET INPUT INPUT INPUT INPUT IN...

Page 18: ...Page 18 of 28...

Page 19: ...Page 19 of 28...

Page 20: ...Page 20 of 28...

Page 21: ...Page 21 of 28...

Page 22: ...Page 22 of 28...

Page 23: ...Page 23 of 28...

Page 24: ...ea Blvd Mississauga Ontario L4W 2T7 Door 3 Operator Door 2 Operator Door 1 Operator LED 1 CX 33 LED 2 LED 3 Relay 1 Relay 2 Relay 3 N C N C N O N O N O N C COM COM COM POWER 12 24V AC DC DRY 1 DRY 2 D...

Page 25: ...UL Approval or certification for this mode 2 Timer H1 sets the length of time the Push Panic switch must be pressed held before the door unlocks 3 Timer H2 sets the minimum ON time for the electric lo...

Page 26: ...2 24V AC DC DRY 1 DRY 2 DRY 3 DRY 4 WET INPUT INPUT INPUT INPUT INPUT MENU UP DOWN 1 2 3 4 5 6 7 8 9 Lock Down PUSH TO LOCK DOWN PUSH TO RESET Lock Down Indicator Can be part of Lock Down Switch Fail...

Page 27: ...DC DRY 1 DRY 2 DRY 3 DRY 4 WET INPUT INPUT INPUT INPUT INPUT MENU UP DOWN Electric Lock Door 1 Power for Strike Activating Switch Door 2 sequences relays 3 to 1 to 2 Door 1 Operator Door 2 Operator S...

Page 28: ...ric Lock Door 1 Power for Strike Activating Switch Door 2 sequences relays 3 to 1 to 2 Door 1 Operator Door 2 Operator Switch Sequences Relays 1 2 only Switch activates Relay 3 only Optional Switches...

Reviews: