Call: 1.877.226.3369 / 905.366.3377
Visit: www.camdencontrols.com
Opening New Doors to
Innovation, Quality and Support!
Page 9 of 9
CX-DE1200 Delayed Egress Electro Magnetic Lock
INSTALLATION INSTRUCTIONS
CX-DESPK15
15 Watt
Speaker
Plug in
Power Supply
12 VDC
PWR
+
_
PWR
+
_
GRN Rly
NO C NC
RED Rly
NO C NC
Ex-Trig
NO C
Reset
NO C
R-Exit
NO C
Bypass
NO C
+
_
_
_
_
+
+
GND
INL
+
CX-TRP-612DC
CM-1100/7212
Remote
Reset Station
Ex. Spkr
+
_
PWR
+
_
PWR
+
_
Ex. Spkr
+
_
PWR
+
_
PWR
+
_
Lock
+
_
Fire P
C NC
Lock
+
_
Fire P
C NC
CM-DE502SO
Remote
Audible-Visual
Station
PWR
+
_
PWR
+
_
GRN Rly
NO C NC
RED Rly
NO C NC
Ex-Trig
NO C
Reset
NO C
R-Exit
NO C
Bypass
NO C
Red
Green
B
CM-DESPK
Remote
Audio
Annunciator
+
_
9. ACCESSORIES WIRING
10. COMPLETE WIRING OPTIONS AND FUNCTIONS
File: CX-DE1200_Manual_R3.indd
Rev/Date.: 2/11/25/21
Part no.: 40-82B236
Page 6
Terminal Descriptions
Ex. Spkr
PWR
+ -
NO C NC
+
-
Fire P
C NC
Lock
GRN Rly
RED Rly
Ex-Trig
Reset R-Exit
Bypass
+
-
NO C NC
NO C NO C NO C
NO C
Wire to
External
Speaker
(CX-DESPK
or
CX-DESPK15)
Power
Supply
Input
12/24 DC
+/- 10%
Lock
Secure
Output
Alarm
Output
Remote
Lock Reset
Input
(Wire to
CM-DESPK)
Remote
Request to
Exit
(Wire from
remote key
switch)
Instant Bypass
Overide Input
PWR
DPS
NO C NC
Bond-S
NO C NC
ATS
NO C NC
Door
Position
Status
(This contact
will change
state when the
maglock is
NOT on the
armature)
Anti Tamper
Switch
(This contact
will change
state when the
cover is
removed.)
External
Trigger
(Wire from of
Tandem
CX-DE1220
lock.)
+
-
Power
Supply for
accessories
Fire Alarm
Input
(Supervised,
Normally
Closed)
[J10 jumper
must be
removed]
Wire
connection
to Tandum
Lock
CX-DE1220
Lock Status
(The bond
sensor will
monitor the
surface of the
armature. This
contact will
change state
when the
electromagnetic
lock is not
generating full
holding
potential.)
Both contacts will be triggered during the
countdown before the maglock is
de-engergized and released.
(The contact
will change
state when
the maglock
coil is
energized or
not
energized.)
(The contact
will change
state when
the alarm
has been
triggered by
a person
pressing on
the door to
exit.)
WARNING: Improper installation, maintenance, inspection or usage of the product or any related accessories or parts may cause the electromagnetic lock, armature
plate and associated hardware to disengage and fall, causing serious bodily injury and property damage. Camden will not be liable to the installer, purchaser, end
user or anyone else for damage or injury to person or property due to improper installation, care, storage, handling, maintenance, inspection, abuse, misuse or act of
God or nature involving this product or any related accessories or parts. The delayed egress device should be routinely checked for proper operation and compliance
with fire and building codes. Refer to maintenance document #40-82B292 for additional information.