background image

CX-PS150UL Power Supply

INSTALLATION INSTRUCTIONS

Page 4 of 4

Call: 1.877.226.3369 / 905.366.3377 

Visit: www.camdencontrols.com

Opening New Doors to  

Innovation, Quality and Support!

File:  CX-PS150UL Power Supply Manual.

indd 

Rev.: October 11,

 

2023

Part No.: 40-82B301

Jumper

Default

Fire Input Triggered/Reset

Auto Reset after AC Mains Lost/Restored

JL OFF Triggered 3X

Drops Power/Manual

Manual

JL ON Triggered 3X

Yes

Drops Power/Auto

Manual

JL OFF Triggered 4X

Drops Power/Manual

Auto

JL ON Triggered 4X

Drops Power/Auto

Auto

The JL jumper has 4 modes: Auto Reset, Manual Reset, Auto Restore AC Mains, Manual Reset AC Mains. 

1.  Latching Output (Auto Reset).

 

  When the JL jumper is ON (shorting both pins) it is in latching mode (auto reset). When the Fire Input is closed the output power is dropped, it will  

  restore power when the Fire Input is open.

2.  Non-Latching (Manual Reset).

 

  When the JL jumper is OFF (both pins open) it is not in latching mode (manual reset). When the Fire Input is closed and the output power is  

  dropped, it will not restore power when the Fire Input is open, but only when the RESET input is used.

3) Mains Fail (Manual Reset).

 

  Using the provided Camden Set Switch tool, place the connector end over the two pins marked as JL. Press the switch 3X (0.5 second per press). The  

  outputs now will not restore when the AC Mains are restored. It will need a manual reset to restore the outputs.

4) Mains Fail (Auto Reset).

 

  Using the provided Camden Set Switch tool, place the connector end over the two pins marked as JL. Press the switch 4X (0.5 second per press). The  

  outputs now will auto restore when the AC Mains are restored. 

Note: 

After setting the AC Mains Fail mode, ensure you place the JL jumper on the JL pins if needed. Refer to the table below for what your application 

requires.

The JL Jumper Modes and Their Functions:

Reviews: