WC16PS SERIES RESTROOM CONTROL

INSTALLATION INSTRUCTIONS

Wiring the Outside WAVE TO OPEN Sensor 
(CM-331/42WS-SGLR) 

Wire in power to the TB1 terminal block on the back lower left 
side (not polarity sensitive). On terminal block TB3, wire the 
common and normally open poles of the relay to Dry1 & Input 
on the CX-33. The Remote terminal (TB2) will be wired in parallel 
with the Remote terminal (TB2) of the Inside WAVE TO LOCK. 

Then it’s wired to Relay 3 (common & normally open) of the 
CX-33. Install the SGLR (light ring) circuit board on the front-face 
of the Outside WAVE TO OPEN sensor.

Confirm the DIP switch settings using the legend below. Adjust 
the range accordingly with POT1 and POT 2 for the desired 
activation time.

Wiring the Inside WAVE TO OPEN Sensor 

(CM-325/42WS)

Wire in power using the two red wires (not polarity sensitive). 
Next, connect the Blue wire (normally open) and the green wire 
(common) to Dry2 & Input on the CX-33. 

The range and the activation time can be adjusted from the 
front-face of the sensor. The range adjustment is on the top and 
the activation time is located on the bottom.

Wiring the Inside WAVE TO LOCK Sensor 

(CM-331/43WS)

Wire in power to the TB1 terminal block on the back lower left 
side (not polarity sensitive).

On terminal block TB3, wire the common and normally open 
poles of the relay to Dry3 & Input on the CX-33.

The Remote terminal (TB2) will be wired in parallel with the 
Remote terminal (TB2) of the Outside WAVE TO OPEN. Then it’s  
wired to Relay 3 (common & normally open) of the CX-33. 
Install the SGLR (light ring) circuit board on the front-face of the 
Inside WAVE TO LOCK sensor.

Confirm the DIP switch settings using the legend below. Adjust 
the range accordingly with POT1 and POT2 for the desired 
activation time.

Once all field devices are wired to the CX-WC16PS then AC 
power can be wired in.
IMPORTANT: Do not apply power to the unit until you 
have fully read the instructions and have made the 
required adjustments.

The supplied CX-TRX-5024 transformer will have its secondary 
terminals wired to the terminals on the top of the left terminal 
strip marked as “AC”.

Next, wire the primary terminals to the AC feed to be used. 
Confirm your connections and apply power by turning on the 
electrical panels breaker.

Selecting a Mode

The CX-WC16PS has two Restroom applications built in (Mode 7 
& 8). The default mode for the CX-WC16PS is Mode 7 
(normally unlocked).

Determining which mode is correct for you will be based on 
whether the Restroom will be normally unlocked (Mode 7) or 
normally locked (Mode 8).

There are three LED displays that will allow you to see what mode 
you have selected when advancing through the modes.

To change the mode of the CX-WC16PS, simply press the 
MENU button once and use the UP button to advance to the 
desired mode.

Editing the Settings for a Mode 

Camden builds in typical times for lock release and door 
operator activation and is ready to use without changing any 
parameters. If you need to change the timing or delay for an 
output, it can be done by pressing the “MENU” button within the 
mode you selected.

Once the option is selected you can use the “UP or DOWN” 
buttons to select the timing needed. The first option 
(H & 1 flashing) will be how long relay 1 will be activated for 
(0-50 seconds).

The second option (d & 1 flashing) will be how long to wait 
before activating relay 2 (0-15 seconds).

The third option (H & 2 flashing) will be how long relay 2 will be 
activated for (0-50 seconds).

The fourth option (d & 2 flashing) will be how long to wait before 
activating relay 3 (0-15 seconds).

The fifth option (H & 3 flashing) will be how long relay 3 will be 
activated for (0-50 seconds). See chart below.

Factory Reset (Defaulting the CX-33)

To return the CX-33 back to its factory default settings you will 
need to remove power, then hold down the “MENU” button 
while powering up the CX-33.

Once started you will see the firmware version listed then a 
number “1” will be displayed. Reconnect your power and press 
the “MENU” button once then use the “UP” or “DOWN” button to 
advance to the desired mode.

Fully test the operation of the CX-WC16PS for proper 
functionality.

Summary of Contents for CX-WC16PS Series

Page 1: ...asily seen by patrons at a distance 2 INSTALLATION Operation at a Glance When the outside WAVE TO OPEN touchless switch is activated it will trigger its N O relay contact to send a momentary closure t...

Page 2: ...ustments The supplied CX TRX 5024 transformer will have its secondary terminals wired to the terminals on the top of the left terminal strip marked as AC Next wire the primary terminals to the AC feed...

Page 3: ...0 0 to 10 seconds 1 Set Dry Input 1 to activate on normally open or normally closed contact N O OR N C 2 Set Dry Input 2 to activate on normally open or normally closed contact N O OR N C 3 Set Dry I...

Page 4: ...Make the electrical connections to the device according to the wiring section 4 Using the dip switch located on the end of the unit set the operating mode 5 Attach the unit to the enclosure using the...

Page 5: ...ox ensure the box is plumb and square and flush with the wall surface then attach the metal adaptor plate included in the packages to the box using appropriate fasteners 2 Bring your 4 or 6 conductor...

Page 6: ...et Surface Mount Enclosure 6 32 x 3 4 2 Pcs 6 32 x 1 2 2 Pcs Polypropylene Lens Holder Set CM 331 43S Sealing Gasket IR Lens CM 331 43S Faceplate CM 331 42SW SGLR CM 325 42SW Faceplate Flush Smooth Wa...

Page 7: ...screws and lockwashers 6 Secure M5x12 screws holding mounting brackets to jamb 4 Installation Mounting Bracket Spacer Spacer Option Spacer M5x12 Flat Head Screw 2pcs Jamp M5x12 Screw Vertical Centerli...

Page 8: ...een input wires Fail Safe Changing Fail Secure 24VDC Red 24V Black Blue Green Ground How to modify fail safe to fail secure or vice versa 1 Loosen the screw as per the product diagram below 2 Rotate t...

Page 9: ...60 81C010FE Decal Print English French Sign WAIT FOR DOOR TO CLOSE 8 60 81C011 Decal Print English Sign OCCUPIED WHEN RED VACANT WHEN GREEN Single Gang SureWave Enclosure 9 CM 34BL Single Gang Black A...

Page 10: ...C16PS SERIES RESTROOM CONTROL INSTALLATION INSTRUCTIONS Page 10 of 13 File WC16PS Restroom Controls Manual indd Rev September 13 2023 Part No 40 82B239 Questions Call us toll free at 1 877 226 3369 or...

Page 11: ...DEN DOOR CONTROLS ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CAMDEN DOOR CONTROLS IS PROHIBITED Place Sign On The Door Inside The Restroom At Eye Level INSIDE THE RESTROO...

Page 12: ...ll System is installed Door Operator 120 VAC N C AC AC Outside Push To Open Inside Push To Open Push To Lock DPS NC DPS COMM WET INPUT Strike Strike Door Operator LED Control VDC VDC 1 2 3 4 CM AF540S...

Page 13: ...Page 13 of 13 WC16PS SERIES RESTROOM CONTROL INS TA LLATIO N INS TR UCTIO NS CABINET BASE L C L C 7 7 8 200 2 mm Cabinet Base Mounting Template 6 152 7 mm 6 152 7 mm 9 5 8 243 9 mm 11 1 16 281 4 mm...

Reviews: