background image

CX-WC17VR-PS SERIES RESTROOM KIT

INSTALLATION INSTRUCTIONS

CX-WC17VR-PS SERIES RESTROOM KIT

INSTALLATION INSTRUCTIONS

4. CX-ED2079 ‘universal’ electric strike installation

1.  Firstly, verify that voltage required to operate Electric strike is compati-

ble with supply voltage of the installation.  

POWER: Red/Black, Blue/Green (12 VDC) 

                Red, Black/Blue, Green (24 VDC) 

           Red/Green (Sort Black, Blue)

2.  Splice the strike wire with the supplied wire and make sure to attach 

provided varistor as described in connection section. 

3.  Make sure that the door jamb has an appropriate cutout to accommo-

date strike assembly. (Make sure to leave enough room for splicing 

between power supply and electric strike wiring.)

4.  For a wooden door jamb, drill holes to install the strike and finally use 

supplied #12 x 1/2” machine screws to secure the strike.

CX-ED2079 ‘Universal’ Electric Strike

1. Prepare the door jamb as per the appropriate drawing.
2. Install mounting brackets to jamb using M5x12 screws

and pressed metal nuts. Do not tighten.

faceplate into jamb. Add one of more spacers between

jamb and mounting bracket when face plate extends

beyond the jamb. When the faceplate sits inside the

jamb, spacers must be added between the mounting

bracket & the lip bracket. Make sure clearance hole in 

spacer aligns with hole in mounting bracket.

4. Connect wires coming from the low voltage side of the

transformer to wires (black) from strike.

5. Install electric strike jamb by attaching with # 10-32

screws and lockwashers.

6. Secure M5x12 screws holding mounting brackets to jamb.

4. Installation

Mounting Bracket

Spacer

Spacer (Option)

Spacer 

M5x12 Flat-Head Screw (2pcs)

Jamp

M5x12 Screw

Vertical Centerline

Note: The products are intended to be installed in accordance 

with the installation wiring diagram, mechanical assembly 

drawings provided with each product, the local authority having 

jurisdiction (AHJ) and the National Electric Code, NFPA 70. 

When installed in fail secure mode, the local authority shall be 

consulted with regard to the use of possible panic hardware to 

allow emergency exit from the secure area.
The electric door strike shall be installed in such a way and 

in such a location so as to not impair the operation of an 

emergency exit device or panic hardware mounted on the door.

(86mm)

3-3/8”

(187mm)

7-3/8”

(36mm)

1-3/8”

(200mm)

7-7/8”

(86mm)

3-3/8”

(86mm)

3-3/8”

(168mm)

6-3/8”

(31mm)

1-7/32”

(31mm)

1-7/32”

(31mm)

1-7/32”

(105mm)

ESP1B + ESP2B

ESP3B

ESP4B

4-1/8”

(124mm)

4-7/8”

(89mm)

3-1/2”

(155mm)

6-1/8”

(173mm)

6-7/8”

(144mm)

5-11/16”

Note:

•  The products are intended to be installed in accordance with the 

installation wiring diagram, mechanical assembly drawings provided 

with each product, the local authority having jurisdiction (AHJ) and 

the electric code, NFPA 70. When installed in fail secure mode, the 

local authority shall be consulted with the regards to the use of 

possible panic hardware to allow emergency exit from the secure 

area. 

•  The electric door strike shall be installed in such a way and in such 

a location so as to not impair the operation of an emergency exit 

device or panic hardware mounted on the door.  

Page 3 of 9

Page 4 of 9

PROPRIETARY AND CONFIDENTIAL

THE INFORMATION CONTAINED IN THIS
DRAWING IS THE SOLE PROPERTY OF
CAMDEN DOOR CONTROLS.  ANY
REPRODUCTION IN PART OR AS A
WHOLE WITHOUT THE WRITTEN 
PERMISSION OF CAMDEN DOOR
CONTROLS IS PROHIBITED.

5502 Timberlea Blvd.
Mississauga, ON  Canada

L4W 2T7

Tel: (905) 366-3377
www.camdencontrols.com

A.OLISA

24/03/22

CUST

Wave 

Swit

ch wire 

 Cut

-out

Drill 

a Ø 0.

250'

' Hole 

Wall

In-wall 

Elect

rical 

Box

Wall

Mounting without in-wall  
electrical box

Mounting with in-wall  
electrical box

2 1/2'

'

 [64.

77mm]

CM-7536VR 

Hands-Free 

Column™ 

switch 

CM-7536VR 

Hands-Free 

Column™ 

switch 

4. Using a level tool, ensure the base unit is perfectly levelled and mark 4 

mounting locations through the adjustable nylon inset screws onto the 

wall surface (if mounting on drywall, use a pencil, and if mounting on 

concrete wall, use a narrow sharp object for marking).

5. Drill the wall at the four marked locations and tap in the appropriate 

wall plugs. We supply both drywall and concrete anchors for the 

included #14 screws.

6. If mounting the Column Switch on an aluminium post or framing 

section, drill and tap four holes for 1/4”-20 stainless steel machine 

screws (also provided). 

7. Connect all the wires coming from the CX-33PS box to the CM-221 

sensor.

8. Secure the assembly with the provided mounting screw, and insert 

actuation bar which was removed in step 1, and finally secure it with 

End cap. 

IMPORTANT: Do not apply power to the unit until you 

have fully read the instructions and have made the 

required adjustments.

The CX-WC17VR-PS Restroom Control Kit comes with the CX-33PS: Advanced 

Logic Relay, Power Supply and Cabinet, which has a set of two terminal strips. 

Each strip has a clear label for wiring, and it is also pre-wired, which eliminates 

the need for a separate wiring manual for the termination point. However, later 

sections of this manual include detailed wiring diagrams for reference.
 

The left-side terminal strip is used to power CX-33PS, the PUSH to OPEN (both 

exterior and interior) column switches, PUSH to LOCK column switch, the door 

position switch, and the wet trigger. The right switch of the terminal is used to 

power the outputs to drive the strike (Relay 1), door operator (Relay 2), LED 

light (Relay 3), and provide VDC power for the door strike.

There are six wires from CM-221 needs to be connected with terminal strips:

Wire Color (from 

CM-221)

Splicing With

To (CX-33PS)

Red wire

-

+V DC

Black wire

-

-V DC

Yellow wire

-

Green LED

White wire

-

Red LED

Green Wire

Top Switch wire

Inside/Outside Push 

to Open and Push 

to Lock

Blue Wire

Top Switch wire

 

IMPORTANT:

The supplied CX-TRX-5024 transformer will have its secondary terminals 

wired to the terminals on the top of the left terminal strip marked as “AC”. 

Next, wire the primary terminals to the AC feed to be used. Confirm your 

connections and apply power by turning on the electrical panel breaker.

CONNECTIONS

Figure 3.3 Wall Mounting Options

Figure 3.3 Mounting of Base Unit

Table 3.1 Wiring Description for CM221

Figure 4.1 CX-ED2079 Strike Mounting

Figure 4.2 Mounting options for CX-ED2079

L4W 2T7

PERMISSION OF CAMDEN DOOR
CONTROLS IS PROHIBITED.

www.camdencontrols.com

PROPRIETARY AND CONFIDENTIAL

THE INFORMATION CONTAINED IN THIS
DRAWING IS THE SOLE PROPERTY OF
CAMDEN DOOR CONTROLS.  ANY
REPRODUCTION IN PART OR AS A
WHOLE WITHOUT THE WRITTEN 

Tel: (905) 366-3377

5502 Timberlea Blvd.
Mississauga, ON  Canada

Angelo   

08/12/22

CM-753VR Column Switch

2 1/2'

'

 [62.

0mm]

36''

 [914.

3mm]

36''

 [914.

3mm]

2 1/16'

'

 [52.

1mm]

Floor 

Acuat

or 

Base 

Unit

Insert

Screws 

Mount

ing 

Screw 

Wall 

Anchors

Top 

Cap

Note:

While placing actuation bar back, make 

sure that hanger sits perfectly into the slot.

D

C

B

A

A

B

C

D

1

2

3

4

5

6

7

8

8

7

6

5

4

3

2

1

NEXT ASSY

USED ON

APPLICATION

MATERIAL

DRAWN

CHECKED

ENG APPR.

MFG APPR.

Q.A.

COMMENTS:

DATE

NAME

TITLE:

SIZE

B

DWG.  NO.

REV

SCALE: 1:1

UNLESS OTHERWISE SPECIFIED:

SHEET 1 OF 1

DO NOT SCALE DRAWING

DIMENSIONS ARE IN INCHES

TOLERANCES:

FRACTIONAL

± 1/64

ANGULAR: MACH

±0.5

   BEND

±

TWO PLACE DECIMAL

± 0.010

THREE PLACE DECIMAL

± 0.005

PROPRIETARY AND CONFIDENTIAL

THE INFORMATION CONTAINED IN THIS

DRAWING IS THE SOLE PROPERTY OF

CAMDEN DOOR CONTROLS.  ANY

REPRODUCTION IN PART OR AS A

WHOLE WITHOUT THE WRITTEN 

PERMISSION OF CAMDEN DOOR

CONTROLS IS PROHIBITED.

5502 Timberlea Blvd.

Mississauga, ON  Canada

L4W 2T7

Tel: (905) 366-3377

www.camdencontrols.com

Hanger

Slot

End Cap

End Cap

Slot

Hanger

Summary of Contents for CX-WC17VR-PS Series

Page 1: ...eturn the CX 33 back to its factory default settings you will need to remove the power then hold down the MENU button while powering up the CX 33 Once started you will see the firmware version listed then a number 1 will be displayed Reconnect your power and press the MENU button once then use the UP or DOWN button to advance to the desired mode Forproper functionality fully testtheoperationoftheC...

Page 2: ... WITHOUT THE WRITTEN PERMISSION OF CAMDEN DOOR CONTROLS IS PROHIBITED 5502 Timberlea Blvd Mississauga ON Canada L4W 2T7 Tel 905 366 3377 www camdencontrols com A OLISA 24 03 22 CUST Wave Switch wire Cut out Drill a Ø 0 250 Hole Wall In wall Electrical Box Wall Mounting without in wall electrical box Mounting with in wall electrical box 2 1 2 64 77mm CM 7536VR Hands Free Column switch CM 7536VR Han...

Page 3: ...stor is provided to protect strike from spikes Connect varistor between input wires Fail Safe Changing Fail Secure 24VDC Red 24V Black Blue Green Ground How to modify fail safe to fail secure or vice versa 1 Loosen the screw as per the product diagram below 2 Rotate the set plate 180 and slide the plate until it is properly seated 3 Tighten the screw Note For UL 294 UL 1034 compliance the door str...

Page 4: ... magnet 120 VAC N C Model 60 40E033 AC AC Outside Push To Open Inside Push To Open Push To Lock DPS NC DPS COMM WET INPUT Lock Strike Strike Door Operator Green LED Red LED VDC VDC PUSH TO OPEN MOV Door Operator PUSH TO OPEN PUSH TO LOCK 12 to 24 V DC 0 V DC Ground Green LED Red LED Relay Normally Open Relay Common Relay Normally Closed CM221 Mode Pins OPEN Default position Internal mode LED color...

Page 5: ...ed LED Relay Normally Open Relay Common Relay Normally Closed CM221 Mode Pins OPEN Default position Internal mode LED colors will be controlled by the IR Sensor SHORTED Extermal mode LED colors will be controlled by Yellow and White wires Distance Adjustment 2 to 8 5 to 20 cm Turn clockwise to increase range Time Adjustment 0 5 to 20 seconds For ToggleTurn clockwise to increase time delay CM 7536V...

Page 6: ...UIRED BUT NOT INCLUDED WITH THE CX WC17VR PS 6 DOOR OPERATOR SUPPLIED BY OTHERS 3 B A C 6 A 1 CX WC17VR PS OPERATION A THE DOOR IS NORMALLY CLOSED AND UNLOCKED B OPERATING THE EXTERIOR ACTIVE SWITCH OPENS THE DOOR C ONCE INSIDE AND THE DOOR IS CLOSED PRESSING THE COLUMN SWITCH WITH THE LOCK SYMBOL AND PUSH TO LOCK LOCKS THE DOOR THE LIGHT RING AROUND THE VALUEWAVE HANDS FREE SWITCH TURNS FROM GREE...

Reviews: