CX-WC17VR-PS SERIES RESTROOM KIT
INSTALLATION INSTRUCTIONS
CX-WC17VR-PS SERIES RESTROOM KIT
INSTALLATION INSTRUCTIONS
4. CX-ED2079 ‘universal’ electric strike installation
1. Firstly, verify that voltage required to operate Electric strike is compati-
ble with supply voltage of the installation.
POWER: Red/Black, Blue/Green (12 VDC)
Red, Black/Blue, Green (24 VDC)
Red/Green (Sort Black, Blue)
2. Splice the strike wire with the supplied wire and make sure to attach
provided varistor as described in connection section.
3. Make sure that the door jamb has an appropriate cutout to accommo-
date strike assembly. (Make sure to leave enough room for splicing
between power supply and electric strike wiring.)
4. For a wooden door jamb, drill holes to install the strike and finally use
supplied #12 x 1/2” machine screws to secure the strike.
CX-ED2079 ‘Universal’ Electric Strike
1. Prepare the door jamb as per the appropriate drawing.
2. Install mounting brackets to jamb using M5x12 screws
and pressed metal nuts. Do not tighten.
faceplate into jamb. Add one of more spacers between
jamb and mounting bracket when face plate extends
beyond the jamb. When the faceplate sits inside the
jamb, spacers must be added between the mounting
bracket & the lip bracket. Make sure clearance hole in
spacer aligns with hole in mounting bracket.
4. Connect wires coming from the low voltage side of the
transformer to wires (black) from strike.
5. Install electric strike jamb by attaching with # 10-32
screws and lockwashers.
6. Secure M5x12 screws holding mounting brackets to jamb.
4. Installation
Mounting Bracket
Spacer
Spacer (Option)
Spacer
M5x12 Flat-Head Screw (2pcs)
Jamp
M5x12 Screw
Vertical Centerline
Note: The products are intended to be installed in accordance
with the installation wiring diagram, mechanical assembly
drawings provided with each product, the local authority having
jurisdiction (AHJ) and the National Electric Code, NFPA 70.
When installed in fail secure mode, the local authority shall be
consulted with regard to the use of possible panic hardware to
allow emergency exit from the secure area.
The electric door strike shall be installed in such a way and
in such a location so as to not impair the operation of an
emergency exit device or panic hardware mounted on the door.
(86mm)
3-3/8”
(187mm)
7-3/8”
(36mm)
1-3/8”
(200mm)
7-7/8”
(86mm)
3-3/8”
(86mm)
3-3/8”
(168mm)
6-3/8”
(31mm)
1-7/32”
(31mm)
1-7/32”
(31mm)
1-7/32”
(105mm)
ESP1B + ESP2B
ESP3B
ESP4B
4-1/8”
(124mm)
4-7/8”
(89mm)
3-1/2”
(155mm)
6-1/8”
(173mm)
6-7/8”
(144mm)
5-11/16”
Note:
• The products are intended to be installed in accordance with the
installation wiring diagram, mechanical assembly drawings provided
with each product, the local authority having jurisdiction (AHJ) and
the electric code, NFPA 70. When installed in fail secure mode, the
local authority shall be consulted with the regards to the use of
possible panic hardware to allow emergency exit from the secure
area.
• The electric door strike shall be installed in such a way and in such
a location so as to not impair the operation of an emergency exit
device or panic hardware mounted on the door.
Page 3 of 9
Page 4 of 9
PROPRIETARY AND CONFIDENTIAL
THE INFORMATION CONTAINED IN THIS
DRAWING IS THE SOLE PROPERTY OF
CAMDEN DOOR CONTROLS. ANY
REPRODUCTION IN PART OR AS A
WHOLE WITHOUT THE WRITTEN
PERMISSION OF CAMDEN DOOR
CONTROLS IS PROHIBITED.
5502 Timberlea Blvd.
Mississauga, ON Canada
L4W 2T7
Tel: (905) 366-3377
www.camdencontrols.com
A.OLISA
24/03/22
CUST
Wave
Swit
ch wire
Cut
-out
Drill
a Ø 0.
250'
' Hole
Wall
In-wall
Elect
rical
Box
Wall
Mounting without in-wall
electrical box
Mounting with in-wall
electrical box
2 1/2'
'
[64.
77mm]
CM-7536VR
Hands-Free
Column™
switch
CM-7536VR
Hands-Free
Column™
switch
4. Using a level tool, ensure the base unit is perfectly levelled and mark 4
mounting locations through the adjustable nylon inset screws onto the
wall surface (if mounting on drywall, use a pencil, and if mounting on
concrete wall, use a narrow sharp object for marking).
5. Drill the wall at the four marked locations and tap in the appropriate
wall plugs. We supply both drywall and concrete anchors for the
included #14 screws.
6. If mounting the Column Switch on an aluminium post or framing
section, drill and tap four holes for 1/4”-20 stainless steel machine
screws (also provided).
7. Connect all the wires coming from the CX-33PS box to the CM-221
sensor.
8. Secure the assembly with the provided mounting screw, and insert
actuation bar which was removed in step 1, and finally secure it with
End cap.
IMPORTANT: Do not apply power to the unit until you
have fully read the instructions and have made the
required adjustments.
The CX-WC17VR-PS Restroom Control Kit comes with the CX-33PS: Advanced
Logic Relay, Power Supply and Cabinet, which has a set of two terminal strips.
Each strip has a clear label for wiring, and it is also pre-wired, which eliminates
the need for a separate wiring manual for the termination point. However, later
sections of this manual include detailed wiring diagrams for reference.
The left-side terminal strip is used to power CX-33PS, the PUSH to OPEN (both
exterior and interior) column switches, PUSH to LOCK column switch, the door
position switch, and the wet trigger. The right switch of the terminal is used to
power the outputs to drive the strike (Relay 1), door operator (Relay 2), LED
light (Relay 3), and provide VDC power for the door strike.
There are six wires from CM-221 needs to be connected with terminal strips:
Wire Color (from
CM-221)
Splicing With
To (CX-33PS)
Red wire
-
+V DC
Black wire
-
-V DC
Yellow wire
-
Green LED
White wire
-
Red LED
Green Wire
Top Switch wire
Inside/Outside Push
to Open and Push
to Lock
Blue Wire
Top Switch wire
IMPORTANT:
The supplied CX-TRX-5024 transformer will have its secondary terminals
wired to the terminals on the top of the left terminal strip marked as “AC”.
Next, wire the primary terminals to the AC feed to be used. Confirm your
connections and apply power by turning on the electrical panel breaker.
CONNECTIONS
Figure 3.3 Wall Mounting Options
Figure 3.3 Mounting of Base Unit
Table 3.1 Wiring Description for CM221
Figure 4.1 CX-ED2079 Strike Mounting
Figure 4.2 Mounting options for CX-ED2079
L4W 2T7
PERMISSION OF CAMDEN DOOR
CONTROLS IS PROHIBITED.
www.camdencontrols.com
PROPRIETARY AND CONFIDENTIAL
THE INFORMATION CONTAINED IN THIS
DRAWING IS THE SOLE PROPERTY OF
CAMDEN DOOR CONTROLS. ANY
REPRODUCTION IN PART OR AS A
WHOLE WITHOUT THE WRITTEN
Tel: (905) 366-3377
5502 Timberlea Blvd.
Mississauga, ON Canada
Angelo
08/12/22
CM-753VR Column Switch
2 1/2'
'
[62.
0mm]
36''
[914.
3mm]
36''
[914.
3mm]
2 1/16'
'
[52.
1mm]
Floor
Acuat
or
Base
Unit
Insert
Screws
Mount
ing
Screw
Wall
Anchors
Top
Cap
Note:
While placing actuation bar back, make
sure that hanger sits perfectly into the slot.
D
C
B
A
A
B
C
D
1
2
3
4
5
6
7
8
8
7
6
5
4
3
2
1
NEXT ASSY
USED ON
APPLICATION
MATERIAL
DRAWN
CHECKED
ENG APPR.
MFG APPR.
Q.A.
COMMENTS:
DATE
NAME
TITLE:
SIZE
B
DWG. NO.
REV
SCALE: 1:1
UNLESS OTHERWISE SPECIFIED:
SHEET 1 OF 1
DO NOT SCALE DRAWING
DIMENSIONS ARE IN INCHES
TOLERANCES:
FRACTIONAL
± 1/64
ANGULAR: MACH
±0.5
BEND
±
TWO PLACE DECIMAL
± 0.010
THREE PLACE DECIMAL
± 0.005
PROPRIETARY AND CONFIDENTIAL
THE INFORMATION CONTAINED IN THIS
DRAWING IS THE SOLE PROPERTY OF
CAMDEN DOOR CONTROLS. ANY
REPRODUCTION IN PART OR AS A
WHOLE WITHOUT THE WRITTEN
PERMISSION OF CAMDEN DOOR
CONTROLS IS PROHIBITED.
5502 Timberlea Blvd.
Mississauga, ON Canada
L4W 2T7
Tel: (905) 366-3377
www.camdencontrols.com
Hanger
Slot
End Cap
End Cap
Slot
Hanger