TEL (+39) 0422 4940 - FAX (+39) 0422 4941 - info@came.com - www.came.com
4.5 Checking the sensor installation
Once mounting work has been completed, the sensor must be tested to ensure it is
functioning correctly. Measure the resistances by actuating the sensor at several points:
Sensor actuated: ≤ 500 ohm
Sensor not actuated with 8.2 kOhm resistor plug: resistance between 8.0 and 9.0 kOhm
5
Commissioning
Once the sensor has been installed, it must be connected to the control unit.
The operating instructions for the corresponding control unit
must be followed when making the connection as well as when
carrying out subsequent installation and commissioning work.