FA00150-EN v.7 - 06/2017
30
CAME S.p.A.
13.3 ADVANCED PARAMETERS MENU
Using the buttons ↑ and ↓ select ADV, press ENTER to select and adjust the following advanced parameters.
Display
Description
Factory settings
OSSM
OPENING
SAFETY
MOTION
Setting the slowdown distance of the opening sensors (see 6A/6B terminals). Choose between the
following values:
NO = no slowdown
100 / 200 / 300 / 400 / 500 = the door slows down in the last 100/ 200/ 300/ 400/ 500 mm of opening
YES = the door slows down during the whole opening
500
OSSS
OPENING
SAFETY STOP
Setting the stopping distance of the opening sensors (see 6A/6B terminals). Choose between the
following values:
NO = no stop
100 / 200 / 300 / 400 / 500 = the door stops in the last 100/ 200/ 300/ 400/ 500 mm of opening
NO
TYLK
LOCK TYPE
Selecting type of locking device. Choose between the following values:
LK1 = bistable locking device (SL5LD)
LK2 = safety brake device (SL5SB)
LK1
ELLK
LOCK
OPERATION
TYPE
Selecting type of lock operation. Choose between the following values:
AUTO = unlocked with automatic operation while locked with unidirectional operation and door
closed
UNLK = always unlocked with automatic operation and unidirectional
EMERGENCY
- Automatic setting for Emergency automation.
LOCK = always locked the door closed
AUTO
PUCL
PUSH DOOR
CLOSED
Setting the push on the closed mechanical stop. Choose between the following values:
NO = no push
MIN = light push
MED = medium push
MAX = heavy push
MIN
PIPP
PUSH DOOR
OPEN
Setting of the opening push. Choose between the following values:
NO = no push
YES = push enabled
NO
HOLD
HOLD DOOR
OPEN
Setting the push of keeping the door open. Choose between the following values:
NO = no push
MIN = light push
MED = medium push
MAX = heavy push
NO
PUGO
PUSH & GO
Push opening activation. Choose between the following values:
NO = disable
YES = enable
NO
TAKO
KO-CLOSING
TIME
Open door time setting, after the 1-KO command. Choose between the minimum and maximum:
NO = see MENU > TAC
minimum value = 1 s
maximum value = 30 s
NO
VTAC
VARIABLE
CLOSING
TIME
Automatic closing time variable in relation of pedestrian traffic. Choose between the following values:
NO = disable
YES = enable
YES
MOT
MOTOR
CIRCUIT
Setting the manual friction of the door (only with power supply), by means of the electrical
connection of the motor windings. Choose between the following values:
OC = manual door opening without friction (motor with open circuit windings)
SC = manual door opening with friction (motor with short-circuit windings)
OC