FA00150-EN v.7 - 06/2017
37
CAME S.p.A.
15. START-UP PROCEDURE OF THE AUTOMATIC SLIDING DOOR FOR EMERGENCY EXIT (EMERGENCY)
15.1 Preliminary checks.
At the end of the installation, move the doors manually
and make sure that operation is smooth and without
friction.
Check the solidity of the structure and the proper
attachment of all the screws.
Check the correctness of all electrical connections.
Note: in the case of 1-leaf door for emergency exit with
opening on the left, the carriage must be fixed to the belt
at the top, as indicated in the figure.
15.2 Before connecting any security devices, leave the jumper on terminals safety of electronic control (41-8A, 41-8B, 41-6A,
41-6B, 1-S1, 1-EO, 0-R0 and the resistor between 1-R1).
15.3 Connect the battery and turn on the power supply.
Note: every time you switch on the automation performs a self-test (from 3 to 30 seconds). The first opening and closing
cycle is at low speed to allow the automatic learning.
It is also performed the emergency opening test of the duration of about 10 seconds (the emergency opening test is
repeated every 24 hours).
15.4 To ensure that the electronic control has the factory settings, restore via the menu:
MEM> FSET> YES (confirm by pressing ENTER for 1 second).
15.5 Perform the menu settings as described in Chapter 13. Use OPEN button to perform the opening door, and verify the
correct operation of the door.
Note: the automation automatically detects any obstacles during the closing movement (reversal movement) and opening
(stopping movement).
15.6 Connect one at a time, opening and safety devices to protect the closing cycle of the door, as described in Chapter 12.6,
and verify proper operations.
Note: verify that the
opening access is properly
protected by safety
sensors, in accordance
with the requirements of
the European standard
EN16005 (annex C).
15.7 Connect one at a time, safety devices to protect the opening cycle of the door, as described in Chapter 12.7, and verify
proper operations.
Note: if the gap between the door and the fixed parts meet the
requirements of the European standard EN16005 (Chapter 4.6.2.1.a), the
safety sensors are not needed (X ≤ 100 e Y ≥ 200).
15.8 Connect the function selector device as described in chapter 12.4, and store the badges as described in chapter 13.4.
15.9 In case the locking device is installed, you must also install the signaling device, and connect the N.O. contact of limit
switch to terminals 1-S1 of electronic control.
15.10 Check the emergency opening of the door by disconnecting the power supply.
15.11 At the end of the automation starting, deliver to the owner the user instructions, including all warnings and
information necessary to maintain the security and functionality of the automatic door.
15.12 The EMERGENCY automation is approved for use in emergency exits, and
ensures complete opening of the door in all situations of: alarm, power failure,
fault conditions.
15.13 FLUO-SL automations are feature of label on the right end cap, containing
the required information by European standards EN16005 and EN60335-2-103.
Note: the manufacturer of the automatic sliding door have to add his own label
identifying the installation.