SERIE
RODEO
18
INSTALLATION OF ACCESSORIES (available upon request)
MA7032 - Battery-powered emergency system
This emergency system opens the door in case of power failure. It includes a pair of 12V (1.2Ah) batteries as
well as a circuit card that keeps the batteries charged and distributes power to the automation system.
By using dip switches 9 and 10 (10-way module), the emergency system can be programmed to operate in the
following ways when the power fails:
Note: When functioning is interlocked (see p. 20), the following functions are selected equally for both auto-
mations.
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
9 OFF
Opening only. The doors open and remain open
10 ON
until current returns to the line. The same occurs
even if the MA7041 selector is set to “doors closed”.
9 ON
Closing only. The doors closes and stays closed
10 ON
(even if "door open" has been selected on MA7041)
until the mains power is restored.
9 OFF
Normal functioning. The doors continue to function
10 OFF
until the current in the batteries drops below the
safety level, in which case they stop. If the MA7041
function selector is set to “doors closed”, the doors
can only be opened by entering a command on the
2-M contact.
1
2
3
4
5
6
7
8
9
10
Anti-panic device with constant battery control
Setting dip switch 2 of the 10-way module to the ON position (on the
interlock system, set it on both panels) activates the constant control of
the battery charge buffer, which during normal functioning with 230V
power mains voltage checks the minimum charge of the 20V batteries; if
it falls below this level (on the interlock system the voltage of the batteries
of one of the two automations) the function activates a safety procedure. This procedure consists in the opening
or closing of the doors (depending on the settings of dip switches 9 and 10). For the interlock system, the safety
procedure (signalled by a continual flashing of LED No. 2 on the MASTER panel) causes the doors to open on
both the automatic system. After reset of the batteries, the LED goes out and the system re-starts normally after
an ‘open’ command.
N.B.: For single automation installations, activating the battery control deactivates normal functioning (dip 9
OFF – 10 OFF).
- If function switch MA7041 is installed, make sure that the “
EMERGENCY” function has been selected (which
is indicated by a flashing yellow LED).
- In any event, normal operation with the programmed settings will automatically resume when the mains power
is restored.
Note: in case the MA7041 selector is not connected
and you wish to activate the antipanic function, bond
contacts 1-3 as shown in the figure.
1 2 3 4 5 6 7
RX GND
1 2 3 4 5 6 7
MF9011 - MF9111
SSOLA
MA7041