LEFM 200 Modbus User Manual
IB0147 Rev. 8
December 2010
Page 13
Section 2
The Modbus registers are located as for the 200C electronics in the following registers.
Setup Variable
Holding Register
Variable
Definition
Address
Note
Fluid Pressure
Float
1172
Use these registers to input with values from
the Flow Computer or Plant Computer
Fluid Temperature
Float
1174
Density
Float
1176
Finally, the meter body temperature can be scaled (offset and slope) with the following registers.
Variable Description
Name
Holding
Register
Address
(Float)
Temperature Offset -units are same as
defined in Section 2.9.1)
Offset
3328
Temperature Slope (degrees/degrees) -
units are same as defined in Section 2.9.1)
Slope
3330
2.10
Analog Outputs
The “Units” Holding Register let’s the user select the units for the output interfaces.
2.10.1 Analog Outputs – Units
Units
The Holding Register (102) scales the analog outputs as follows:
2.10.2 Analog Outputs – 200C Electronics Only
Output Scaling B1, A1, B2, A2
B1/B2 are in engineering units and A1/A2 are in counts (0 for minimum range, 65535 for
maximum range).
Analog Output (counts) = A1 +(analog engineering units-B1)*(A2-A1)/(B2-B1),
1 1 2 1
Temperature (°F=0, °C=1)
Pressure (psig =0, kg/cm2=1, bar=2, kPa=3)
Density (g/cc=0, kg/m³=1,API=2,lbm/ft³=3)
Velocity (ft/s - in/s=0, m/s=1)
Summary of Contents for LEFM 200
Page 4: ...IB0147 Rev 08 LEFM 200 Modbus User Manual Table of Contents Page ii December 2010 ...
Page 22: ...IB0147 Rev 08 LEFM 200 Modbus User Manual Section 2 Page 18 December 2010 ...
Page 28: ...IB0147 Rev 08 LEFM 200 Modbus User Manual Section 3 Page 24 December 2010 ...
Page 40: ...IB0147 Rev 08 LEFM 200 Modbus User Manual Section 4 Page 36 December 2010 ...