LEFM 200 Modbus User Manual
IB0147 Rev. 8
December 2010
Page 3
Section 2
2.0 Holding Registers - LEFM 240C(i), LEFM 220C(i),
LEFM280C(i), and SoundTrack
The following table defines the addresses for the software setup variables used by typical users.
*Other address locations not listed here were used by Cameron to customize each meter for its
manufactured dimensions.
Holding Registers are accessed from the 200 Series Electronics with Modbus Function Code 3.
Note: Integer values are limited to ±32767.
2.1
Registers to Save the Setup
Setup Variable Holding
Register
Variable Definition
Address*
Notes
Command to use latest entries
BURN AND USE
Integer
170
Activate new setup
values
Save Setup Lockout (Ci Only)
To place the transmitter in lockout mode put switches 1 -6 in the on position.
In Lockout mode – all write commands (FNC16, FNC6) to holding registers and special action
holding registers (burn and use) sent via Modbus are blocked. A Modbus error code indicating
an illegal address is returned in response. Read commands to holding and input registers (e.g.,
FNC3, FNC4) are still enabled.
2.2
Registers for Scaling Flow, Flow Units and Pulse Output
Setup Variable Holding
Register
Variable
Definition
Address*
Notes
MINIMUM FLOW
CUTOFF
Float
44
Flow rates below this value ( in
absolute value) are clamped to 0
(display and pulses) and the flow
meter’s totalizers do not update.
UNITS CONVERSION
(converts default cubic feet
to other units)
Float
52
Typically delivered in customer
requested units:
Typical Units:
0.178095238 converts to barrels
2.8317E-02 converts to cubic meters
Summary of Contents for LEFM 200
Page 4: ...IB0147 Rev 08 LEFM 200 Modbus User Manual Table of Contents Page ii December 2010 ...
Page 22: ...IB0147 Rev 08 LEFM 200 Modbus User Manual Section 2 Page 18 December 2010 ...
Page 28: ...IB0147 Rev 08 LEFM 200 Modbus User Manual Section 3 Page 24 December 2010 ...
Page 40: ...IB0147 Rev 08 LEFM 200 Modbus User Manual Section 4 Page 36 December 2010 ...