Install & Operating Manual
CleanSeal V3
Main Filter Installation / Exchange
CAUTION:
The media pack of a traditional HEPA filter panel is extremely sensitive.
This is no longer an issue for latest generation filters like Camfil EnerGuard
, but
generally speaking, filters have to be handled with the utmost care to avoid
creating damage during installation.
DO NOT place objects on or manipulate filter panels by touching the media,
even for panels with protective grid.
Handle filter panels by the frame only !
The features of the CleanSeal toolless filter clamping system support safe and easy filter change.
•
For best scanning results
with MIP housings, orient filter with media pleats parallel to the probe
•
Before inserting the filter, make sure all clamping blocks are rotated parallel to the housing wall.
•
Place the filter into the housing on the support rails.
•
Rotate the clamps out over the filter and close clamping levers.
•
For filter deinstallation, proceed in reverse order.
PLEASE NOTE:
Clamping settings will be stable over time, unless clamping levers get rotated
inadvertently. Settings are adjustable,
see § 10.2
CAUTION:
In case of integrity issues at installation, check all possible root causes.
DO NOT overcompress filter gaskets, as gasket damage might result.