Install & Operating Manual
CleanSeal V3
11
Maintenance
CleanSeal Terminal housings don’t require regular maintenance interventions
For best long-term performance, the
following checks are recommended when changing filters
:
•
Check the gasket sealing surface.
If necessary, clean with alcohol on a soft, lint-free cloth.
•
Check condition and firm connection of the measurement port PU tubes.
Aged and/or hardened tubes should be replaced by a new tube (ca. 200mm long)
•
When installing a new filter, check gasket compression.
If necessary, you may adjust by turning the unlocked green clamp handle,
see § 10.2
•
On MIP housings check absence of filings etc. which would indicate a mechanical issue
with excessive wear on the scan drive.
•
For specific intervention procedures,
see § 11.2
or contact your Camfil representative.
.