PM 1000288 000 00
Device handbook SIRAX BT5100
26/32
8. Service, maintenance and disposal
For devices that have not been opened in the factory, no warranty or guarantee can be assumed.
8.1 Repair work and modifications
Repair work and modifications shall exclusively be carried out by the manufacturer. Do not open the housing of the device. In case of any tampe-
ring with the device, the guaranty claim shall lapse. We reserve the right of changing the product to improve it.
DIP Switch setting
ON
1 2 3 4
ON
1 2 3 4
Type of output signal
load-independent
current
load-independent
voltage
NOTE: Black portion in above diagram indicate switch position.
7.2 Programming via the programming connection and the PRKAB5000 programming cable
Follow the subsequent steps to program the SIRAX BT5100 transducer via the programming connection and the PRKAB5000 programming
cable:
Step 1:
DIP switch setting
The DIP switches should be configured for the desired measurement output as
described in Chapter 7.4.
Step 2:
Connection
Connect PC
↔
PRKAB5000
↔
transducer according to diagram.
Please observe that the power supply for the transducer must be connected prior to
programming. The installation position is irrelevant.
Step 3:
Programming
Program is effected via a PC, the CB-Configurator software and the PRKAB5000
programming cable.
The PRKAB5000 programming cable assumes the signal level and also provides the galvanic
isolation between the PC connection and the programming connection at the transducer.
7.3 Programming via the RS485 (Modbus) interface
Follow the subsequent steps to program the transducer via the RS485 interface and Modbus:
Schritt 1: DIP switch setting
The DIP switches must be configured for the desired output type as described in Section 7.4.
Schritt 2: Connection
Connect the Modbus cable according to the connection diagram in Chapter 11.3. Please observe also the information in the Modbus (RS485)
interface definition in Chapter 11.
Schritt 2: Programming
Program SIRAX BT5100 via the Modbus RTU interface and the CB-Configurator software. Please observe the detailed Modbus description in
Chapter 11.
To change the output from current to voltage, enter the value “1”.
To change the output from voltage to current, enter the value “2”.
(See Section 13.2 and Table 2 Parameter No. 16 & 18 for the details).
Connect the power supply to SIRAX BT5100 before programming.
7.4. DIP Switch Setting for Output
To configure SIRAX BT5100 Output, programming method to be adapted
along with mechanical switch setting (DIP switch setting on PCB).
Type of output (current or voltage signal) has to be set by DIP switch.
Remove Sticker for o/p Selection.
PRKAB5000
Power supply
Transducer
Programming connector
CB-Configurator
Transducer
Programming cable