Commissioning and use during operation
Advanced Graphic Data Manager
56
Submenu: Totalization
Settings only required if this analog measuring point is to be integrated
for calculating the volume for example. For analysis periods, see "Signal
analysis".
Fig. 38:
Setup - Inputs - Universal inputs, Universal input x,
submenu "Totalization"
Totalization:
using the totalization function, the volume (in m
3
) can be
calculated from an analog signal (e.g. flow in m
3
/h).
Picklist:
no
, yes
24000/000 to
24000/039
Totalization base:
select the corresponding time base here. Example:
ml/s -> time base
seconds (s)
; m
3
/h -> time base hours (h).
Picklist:
second (s)
, minutes (min), hour (h), day (d)
24005/000 to
24005/039
Total. eng. unit:
here, enter the unit for the volume determined by
totalization (e.g. "m
3
").
24010/000 to
24010/039
Low flow cut off:
specify how the device should execute low flow cut
off.
Picklist:
area around zero point
, absolute value
24015/000 to
24015/039
Low flow cut off:
analog values that are lower than the set threshold
value (absolute value) are not integrated ("low flow cut off").
User input: 6-digit; factory setting:
0
24020/000 to
24020/039
Calc. factor:
factor for converting the integrated value (e.g. the
transmitter returns l/s -> integration base = second -> desired unit is m
-> select 0.001 as the factor).
Picklist: 0.00001 to 10000, free configuration; factory setting:
1
24025/000 to
24025/039
Only if "Free configuration" is
selected for "Calc. factor":
Calc. factor:
user-defined entry of the factor for converting the
integrated value. Factory setting:
1.000
24030/000 to
24030/039
Totalizer:
Initial setting for the totalizer. Useful when continuing
measurements recorded to date with an (electro)-mechanical counter.
Factory setting:
0
24035/000 to
24035/039
"Inputs" menu
items
Configurable parameters
(factory settings are highlighted in bold)
Direct access
code