background image

Operating Instructions

Operating Instructions

Installation (Continued)

OIL LEVEL CHECK (

See Figure 7

)

 •  Check oil level by removing oil plug.
 •  With hot oil, the level will be higher than with cold oil.

As a result, oil may escape when the oil plug is opened at the 
maximum oil level. If this does happen, close the oil plug 
immediately and carefully clean up the oil that has escaped.

NOTE:

 The oil plug is provided with a safety hole on the side 

from which oil or air escapes if there is any residual pressure 
in the air end. Wait for one minute after the unit is at standstill 
before opening the oil plug.

1.  Switch off the system, prevent it from being switched back 

on without authorization.

2.  Wait for one minute at standstill.

3.  Unscrew the oil plug on the filler neck by hand with the air 

end depressurized.

4.  Check the oil level.

5.  If necessary, top off oil of the same oil type and the same 

brand up to the maximum level (see Figure 7 and Lubrication 
section).

NOTE:

 The oil filler neck is positioned so that it is not possible to 

overfill the system. Excess oil runs out of the filler neck.

6.  Screw on the oil plug firmly by hand.

7.  Switch on the system.

8.  Wipe off and clean up any spilled oil.

START-UP INFORMATION

 

READ AND UNDERSTAND ALL STEPS BELOW 

  BEFORE  TURNING ON POWER .

1.  Check oil level (See Figure 7).

2.  If it has been longer than 12 weeks since the compressor has 

been operated the air end 

must

 be primed with 8 ounces of 

oil.

 

 

Before resuming operation, the 

  electrical equipment and all safety-relevant 

units must be checked for leaks and proper function. Loose 
connections must be refastened and damaged lines must be 
replaced.

 

Screw compressor systems that are switched off, shut down, 
or stored for longer than 12 weeks cannot be placed into 
operation again until after the following steps have been 
carried out:

a.  Manually rotate the compact module screw compressor 

in the rotation direction several times.

b.  With the compressor system stopped, add approximately 

8 ounces of oil (same oil type as in the air end) into the 
rotor chamber (see Figure 9).

c.  Once again, manually rotate the compressor module 

compressor stage in the rotation direction several times.

d.  Check the oil level in the air end and top off if necessary 

(see Maintenance section).

e.  Monitor operation of the compressor system for at least 

15 minutes, but at least until the steadystate temperature 
is reached (continuous operating temperature).

3. 

Direction of rotation must be checked.

 Operation of the 

air end for more than 2 seconds in the wrong direction will 
destroy the screw compressor.

4.  Check direction of rotation by quickly bumping the power to 

ON and having someone else watch the motor pulley to see 
which way it turns. Belt guard should remain installed. Also 
check the direction of rotation of the oil cooler fan. The fan 
must suck air in from the wire guard side and push air out 
through the radiator when turning the correct direction. This 
can be checked by holding a small strip of paper in front of 
the radiator. With the correct direction of rotation the paper 
will blow out away from the radiator.

5.  Reset E-Stop switch if needed (see Figure 8). 

6.  Turn on the incoming power at the disconnect switch/circuit 

breaker. The White incoming power indicator lamp will 
illuminate. The motor will not turn on with this step.

7.  Turn the on/off switch to the On position. The green lamp 

will illuminate indication the compressor is ready to run.  
The RED High temperature/High Pressure Failure Lamp will 
illuminate. The motor will not turn on with this step.

8.   Keep your hand on the on/off switch ready to turn off 

immediately after start up to check the rotation direction. 
Also check the direction of the cooler fan.

9.  The motor can now be started by pressing the High temp/

high pressure reset. The red lamp is also a momentary 
contact switch. The motor will start with this step.

10. Immediately turn off the on/off switch. The motor will stop 

with this step.

11. If the direction of rotation is incorrect, disconnect, lock out 

and tag out all incoming power. Change the position of two 
of the incoming power lines and repeat steps 5-10.

12. When the direction of rotation has been confirmed the 

compressor is ready to run for an initial start up operation 
check.

Figure 9 - Air End Priming Location

Prime Port

Prime Port

Pulley

Pulley

12

www.campbellhausfeld.com

Summary of Contents for CS2152

Page 1: ...Information 2 Specifications 2 Getting To Know Your Compressor 4 Unpacking 7 Installation 7 Wiring Diagram 9 Operation 13 Maintenance 14 Troubleshooting Guide 18 Limited Warranty 20 Quick Reference O...

Page 2: ...ts or other reproductive harm Wash hands after handling You can create dust when you cut sand drill or grind materials such as wood paint metal concrete cement or other masonry This dust often contain...

Page 3: ...r than the Maximum Allowable Working Pressure MAWP of the tank MUST be installed in the air lines or in the tank for this compressor The ASME safety valve must have sufficient flow and pressure rating...

Page 4: ...www campbellhausfeld com 4 Operating Instructions Getting To Know Your Compressor Motor Control Box Air End Air Oil Separator Tank Pressure Gauge Tank Safety Valve Oil Filter Tank Drain Oil Drain Oil...

Page 5: ...Figure 2 Components of the compressor www campbellhausfeld com 5 Series CS Rotary Screw Compressors Getting To Know Your Compressor Air Oil Separator Beltguard ASME Label Oil Filter...

Page 6: ...et Electric Control Unit Oil Drain Screw Air Oil Separating Element Compressed Air Outlet Oil Filter Oil Circulation Connection Inlet Oil Circulation Connection Outlet Safety Valve Temperature Sensor...

Page 7: ...th clean dry outside air Supply air should be piped in from external sources TANK MOUNTING The tank should be bolted into a flat even concrete floor or on a separate concrete foundation If using isola...

Page 8: ...ting short circuiting and fire damage will result from inadequate wiring Wiring must be installed in accordance with National Electrical Code and local codes and standards that have been set up coveri...

Page 9: ...N HOUR METER M RESET TR INLET VALVE HATR HATR 2 HATS HPR HPS HPR 2 HATR 3 HPR 3 TR R w TR HPR 1 HATR 1 FOL COL OFF ON ESTOP CT TPs 5 7 14 13 9 5 24 26 CT CONTROL TRANSFORMER COL COIL OVERLOAD FOL FAN...

Page 10: ...as specified in the United States National Electrical Code Chapter 2 Wiring Design and Protection Article 210 using the applicable article For Motors and Motor Controllers Article 430 Table 430 1 52...

Page 11: ...or oil Part number GS903800AV 1 Gallon Container Available from Campbell Hausfeld please call 1 855 504 5678 for customer assistance Oil Capacity 2 1 gallons OIL LEVEL Disconnect tag and lock out powe...

Page 12: ...manually rotate the compressor module compressor stage in the rotation direction several times d Check the oil level in the air end and top off if necessary see Maintenance section e Monitor operatio...

Page 13: ...run for approximately 5 minutes Turn off using the ON OFF switch Allow compressor to sit for at least 1 minute while the high pressure air is released through the compressor inlet You will hear the ai...

Page 14: ...en the tank resulting in damage from rupture or explosion Always replace worn cracked or damaged tanks Drain liquid from tank daily The tank should be carefully inspected at a minimum of once a year L...

Page 15: ...being switched back on without authorization 2 Depressurize the system completely 3 Remove the oil filter cartridge with a suitable tool e g oil filter strap wrench Dispose of the old oil filter cart...

Page 16: ...not remove air filter housing or perform any maintenance with pressure in the air end or air pressure tank Never run the compressor pump without an intake air filter or with a clogged intake air filte...

Page 17: ...for longer than 12 weeks Daily 1 Check the safety valves 2 Drain tank to remove water 3 Check belt tension At 50 operating hours 1 Check the oil level in the air end 2 Tighten all screw pipe fittings...

Page 18: ...at covers this issue Unit starts but does not get to full speed Insufficient power to compressor Source electric to the compressor is either the incorrect voltage insufficient wire size to carry the l...

Page 19: ...Series CS Rotary Screw Compressors www campbellhausfeld com Service Record DATE MAINTENANCE PERFORMED REPLACEMENT COMPONENTS REQUIRED 19...

Page 20: ...the warranty period Warranted repairs will be made at the Purchaser s location 8 RESPONSIBILITIES OF PURCHASER UNDER THIS WARRANTY A Provide dated proof of purchase and maintenance records B Use reas...

Page 21: ...S4 Desempaque S7 Instalaci n S7 Diagrama El ctrico S9 Funcionamiento S13 Mantenimiento S14 Gu a de Resoluci n de Problemas S18 Garant a Limitada S20 Referencia R pida ACEITE Aceite para compresor rota...

Page 22: ...Cuando corta lija taladra o pule materiales como por ejemplo madera pintura metal hormig n cemento u otro tipo de mamposter a se puede producir polvo Con frecuencia este polvo contiene productos qu mi...

Page 23: ...ridad de manejo Mantenga a los visitantes alejados y NUNCA permita la presencia de ni os en el rea de trabajo Siempre use anteojos de seguridad y prot jase los o dos para operar el cabezal o el compre...

Page 24: ...del compresor S4 Motor Caja de control Unidad de compresi n Separador de aire aceite Man metro del tanque V lvula de seguridad del tanque Filtro de aceite Drenaje del tanque Purga del aceite Conjunto...

Page 25: ...Conozca su Compresor Figura 2 Componentes del compresor Separador de aire aceitea Tapa de la correa Etiqueta ASME Filtro de aceite Compresores de Tornillo Rotativo Serie CS S5...

Page 26: ...eite Salida de aire comprimido Filtro de aceite Conexi n y entrada de la circulaci n de aceite Conexi n y salida de la circulaci n de aceite V lvula de seguridad Conexi n del sensor de temperatura Con...

Page 27: ...para suministrarle el aire del exterior MONTAJE DEL TANQUE El tanque debe de ser atornillado a una superficie plana y lisa de concreto o sobre una cimentaci n independiente Si se emplean apoyos de amo...

Page 28: ...seg n los c digos locales y nacionales Si el sistema de alambrado no se instala adecuadamente podr a ocasionar sobrecalentamiento cortocircuitos e incendios El alambrado se debe hacer seg n todos los...

Page 29: ...HATS HPR HPS HPR 2 HATR 3 HPR 3 TR R w TR HPR 1 HATR 1 FOL COL APAGADO ENCENDIDO PARO EMERGENTE CT TPs 5 7 14 13 9 5 24 26 CT CONTROL DEL TRANSFORMADOR COL SOBRECARGA DE BOBINA FOL SOBRECARGA DE VENTI...

Page 30: ...quivocado causar la aver a del compresor La direcci n de rotaci n debe ser en sentido opuesto a las manecillas del reloj tal como lo muestra la flecha en la unidad de compresi n Figura 6 vista frontal...

Page 31: ...i n INSPECCI N DEL NIVEL DE ACEITE ver Figura 7 Inspeccione el nivel de aceite retirando el tap n del aceite Con el aceite caliente el nivel puede estar m s arriba que con el aceite en fr o Como resul...

Page 32: ...n m s que observe la polea del motor para verificar en cual direcci n gira La protecci n de la banda debe permanecer instalada Asimismo verifique la direcci n de rotaci n en el ventilador del enfriado...

Page 33: ...SGO DE QUEMADURAS Las piezas y superficies se calientan Funcionamiento 4 Permita que el compresor funcione por aproximadamente 5 minutos Ap guelo mediante el interruptor de ON OFF Deje que el compreso...

Page 34: ...cuidadosamente cuando menos una vez cada a o Realice la b squeda de fisuras que se forman cerca de las soldaduras Si se detecta una fisura elimine de inmediato la presi n del tanque y sustit yalo Figu...

Page 35: ...sor de tornillo en apagado OFF para prevenir que vuelva a funcionar sin que se le requiera 2 Despresurice el sistema por completo 3 Retire el filtro del aceite con una herramienta adecuada por ejemplo...

Page 36: ...a opere la bomba del compresor sin el filtro de admisi n de aire o con un filtro que se encuentre obstruido El elemento del filtro de aire debe ser verificado mensualmente ver Figura 14 Mantenimiento...

Page 37: ...de 12 semanas Diariamente 1 Verifique las v lvulas de seguridad 2 Drene el tanque para retirar el agua 3 Verifique la tensi n de la banda A las 50 horas de operaci n 1 Verifique el nivel del aceite de...

Page 38: ...restablecimiento del sistema consulte la secci n del manual que cubre este problema La unidad arranca pero no llega a su m xima velocidad Corriente insuficiente para el compresor La fuente el ctrica...

Page 39: ...Registro de Servicio FECHA MAINTENIMIENTO EFECTUADO REPUESTOS REQUERIDOS Compresores de Tornillo Rotativo Serie CS S19...

Page 40: ...ar n en las instalaciones del comprador 8 RESPONSABILIDADES DEL COMPRADOR BAJO ESTA GARANT A A Suministrar prueba fechada de compra y la historia de mantenimiento del producto B Tener cuidado al utili...

Reviews: