Section 7. Installation
7.9.1.5 PulseCountReset Instruction
PulseCountReset
is used in rare instances to force the reset or zeroing of CR1000
pulse accumulators (see
Measurements — Overview
(p. 62))
.
PulseCountReset
is needed in applications wherein two separate
PulseCount()
instructions in separate scans measure the same pulse-input terminal. While the
compiler does not allow multiple
PulseCount()
instructions in the same scan to
measure the same terminal, multiple scans using the same terminal are allowed.
PulseCount()
information is not maintained globally, but for each individual
instruction occurrence. So, if a program needs to alternate between fast and slow
scan times, two separate scans can be used with logic to jump between them. If a
PulseCount()
is used in both scans, then a
PulseCountReset
is used prior to
entering each scan.
7.9.1.6 Scaling Array
CRBasic example
Scaling Array
(p. 177)
demonstrates programming to create and
use a scaling array. Several multipliers and offsets are entered at the beginning of
the program and then used by several measurement instructions throughout the
program.
CRBasic Example 26.
Scaling Array
'This program example demonstrates the use of a scaling array. An array of three
'temperatures are measured. The first is expressed as degrees Celsius, the second as
'Kelvin, and the third as degrees Fahrenheit.
'Declare viewable variables
Public
PTemp_C
Public
Temp_C(3)
Public
Count
'Declare scaling arrays as non-viewable variables
Dim
Mult(3)
Dim
Offset(3)
'Declare Output Table
DataTable
(Min_5,True,-1)
DataInterval
(0,5,Min,0)
Average
(1,PTemp_C,FP2,0)
Maximum
(1,PTemp_C,FP2,0,0)
Minimum
(1,PTemp_C,FP2,0,0)
Average
(3,Temp_C(),FP2,0)
Minimum
(3,Temp_C(1),FP2,0,0)
Maximum
(3,Temp_C(1),FP2,0,0)
EndTable
'Begin Program
BeginProg
'Load scaling array
Mult(1) = 1.0 : Offset(1) = 0
'Scales 1st thermocouple temperature to Celsius
Mult(2) = 1.0 : Offset(2) = 273.15
'Scales 2nd thermocouple temperature to Kelvin
Mult(3) = 1.8 : Offset(3) = 32
'Scales 3rd thermocouple temperature to Fahrenheit
177
Summary of Contents for CR1000
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 36: ......
Page 38: ......
Page 40: ......
Page 60: ...Section 4 System Quickstart Figure 16 PC200W View Line Graph 60 ...
Page 96: ......
Page 98: ...98 ...
Page 302: ......
Page 453: ...Section 8 Operation Figure 115 Using the Keyboard Display 453 ...
Page 456: ...Section 8 Operation Figure 118 Real Time Custom 456 ...
Page 457: ...Section 8 Operation 8 8 1 3 Final Memory Tables Figure 119 Final Memory Tables 457 ...
Page 458: ...Section 8 Operation 8 8 2 Run Stop Program Figure 120 Run Stop Program 458 ...
Page 460: ...Section 8 Operation Figure 122 File Edit 460 ...
Page 461: ...Section 8 Operation 8 8 4 PCCard Memory Card Display Figure 123 PCCard CF Card Display 461 ...
Page 478: ......
Page 506: ......
Page 536: ......
Page 636: ......
Page 642: ......
Page 644: ......
Page 676: ......
Page 677: ......