Section 7. Installation
5. To simulate seven-day-service calibration conditions (30 mg/l standard
solution), the variable
KnownSalinity
remains at
30.0
. Change the value in
variable
CalMode
to
1
to start the calibration. When
CalMode
increments to
6
,
the seven-day-service offset calibration is complete. Calibrated offset will
equal
-37.23
mg/l.
CRBasic Example 41.
FieldCal()
Offset
'This program example demonstrates the use of FieldCal() in calculating and applying an
'offset calibration. An offset calibration compares the signal magnitude of a sensor to a
'known standard and calculates an offset to adjust the sensor output to the known value.
'The offset is then used to adjust subsequent measurements.
'This program demonstrates the offset calibration with the following procedure:
' -- Simulate a signal from a salinity sensor.
' -- Measure the 'sensor' signal.
' -- Calculate and apply an offset.
'
'You can set up the simulation by loading this program into the CR1000 and interconnecting the
'following terminals with a jumper wire to simulate the salinity sensor signal as follows:
'
Vx1
---
SE
1
'For the simulation, the value of the calibration standard and the initial 'sensor' signal
'are set automatically. Start the calibration routine by setting variable CalMode = 1. When
'CalMode = 6 (will occur automatically after 10 measurements), the routine is complete.
'Note the new value in variable SalinityOffset. Now enter the following millivolt value as
'the simulated sensor signal and note how the new offset is added to the measurement:
' SimulatedSalinitySignal = 1345
'NOTE: This program places a .cal file on the CPU: drive of the CR1000. The .cal file must
'be erased to reset the demonstration.
'DECLARE SIMULATED SIGNAL VARIABLE AND SET INITIAL MAGNITUDE
Public
SimulatedSalinitySignal = 1350
'mg/l
'DECLARE CALIBRATION STANDARD VARIABLE AND SET MAGNITUDE
Public
KnownSalinity = 30
'mg/l
'DECLARE MEASUREMENT RESULT VARIABLE.
Public
Salinity
'DECLARE OFFSET RESULT VARIABLE
Public
SalinityOffset
'DECLARE VARIABLE FOR FieldCal() CONTROL
Public
CalMode
'DECLARE DATA TABLE FOR RETRIEVABLE CALIBRATION RESULTS
DataTable
(CalHist,NewFieldCal,200)
SampleFieldCal
EndTable
217
Summary of Contents for CR1000
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 36: ......
Page 38: ......
Page 40: ......
Page 60: ...Section 4 System Quickstart Figure 16 PC200W View Line Graph 60 ...
Page 96: ......
Page 98: ...98 ...
Page 302: ......
Page 453: ...Section 8 Operation Figure 115 Using the Keyboard Display 453 ...
Page 456: ...Section 8 Operation Figure 118 Real Time Custom 456 ...
Page 457: ...Section 8 Operation 8 8 1 3 Final Memory Tables Figure 119 Final Memory Tables 457 ...
Page 458: ...Section 8 Operation 8 8 2 Run Stop Program Figure 120 Run Stop Program 458 ...
Page 460: ...Section 8 Operation Figure 122 File Edit 460 ...
Page 461: ...Section 8 Operation 8 8 4 PCCard Memory Card Display Figure 123 PCCard CF Card Display 461 ...
Page 478: ......
Page 506: ......
Page 536: ......
Page 636: ......
Page 642: ......
Page 644: ......
Page 676: ......
Page 677: ......