Section 8. Operation
The CR1000 measures analog voltage by integrating the input signal for a fixed
duration and then holding the integrated value during the successive
approximation analog-to-digital (A-to-D) conversion. The CR1000 can make and
store measurements from up to eight differential or 16 single-ended channels
configured from
H/L
terminals at the minimum scan interval of 10 ms (100 Hz)
using fast-measurement-programming techniques as discussed in
Measurements:
Faster Analog Rates
(p. 229).
The maximum conversion rate is 2000 per second (2
kHz) for measurements made on a one single-ended channel.
Table 54.
CRBasic Parameters Varying Measurement Sequence and
Timing
CRBasic Parameter
Description
MeasOfs
Correct ground offset on single-ended measurements.
SettlingTime
Sensor input settling time.
Integ
Duration of input signal integration.
RevDiff
Reverse high and low differential inputs.
RevEx
Reverse polarity of excitation voltage.
Measurement Integration
Integrating the signal removes noise that creates error in the measurement. Slow
integration removes more noise than fast integration. Integration time can be
modified to reject 50 Hz and 60 Hz mains-power line noise.
Fast integration may be preferred at times to,
•
minimize time skew between successive measurements.
•
maximize throughput rate.
•
maximize life of the CR1000 power supply.
•
minimize polarization of polar sensors such as those for measuring
conductivity, soil moisture, or leaf wetness. Polarization may cause
measurement errors or sensor degradation.
improve accuracy of an LVDT measurement. The induced voltage in an LVDT
decays with time as current in the primary coil shifts from the inductor to the
series resistance; a long integration time may result in most of signal decaying
before the measurement is complete.
Single-Ended Measurements — Details
Related Topics:
•
Single-Ended Measurements — Overview
(p. 65)
•
Single-Ended Measurements — Details
(p. 307)
With reference to the figure
Programmable Gain Input Amplifier (PGIA)
(p. 306),
during a single-ended measurement, the high signal (H) is routed to V+. The low
signal (L) is automatically connected internally to signal ground with the low
signal tied to ground ( ) at the wiring panel. V+ corresponds to odd or even
307
Summary of Contents for CR1000
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 36: ......
Page 38: ......
Page 40: ......
Page 60: ...Section 4 System Quickstart Figure 16 PC200W View Line Graph 60 ...
Page 96: ......
Page 98: ...98 ...
Page 302: ......
Page 453: ...Section 8 Operation Figure 115 Using the Keyboard Display 453 ...
Page 456: ...Section 8 Operation Figure 118 Real Time Custom 456 ...
Page 457: ...Section 8 Operation 8 8 1 3 Final Memory Tables Figure 119 Final Memory Tables 457 ...
Page 458: ...Section 8 Operation 8 8 2 Run Stop Program Figure 120 Run Stop Program 458 ...
Page 460: ...Section 8 Operation Figure 122 File Edit 460 ...
Page 461: ...Section 8 Operation 8 8 4 PCCard Memory Card Display Figure 123 PCCard CF Card Display 461 ...
Page 478: ......
Page 506: ......
Page 536: ......
Page 636: ......
Page 642: ......
Page 644: ......
Page 676: ......
Page 677: ......