Section 8. Operation
P Terminals
•
Maximum input frequency is dependent on input voltage:
o
1.0 to 20 Hz at 20 mV RMS
o
0.5 to 200 Hz at 200 mV RMS
o
0.3 to 10 kHz at 2000 mV RMS
o
0.3 to 20 kHz at 5000 mV RMS
•
CRBasic instruction:
PulseCount()
Internal ac coupling is used to eliminate dc-offset voltages of up to
±
0.5 Vdc.
C Terminals
Low-level ac signals cannot be measured directly by
C
terminals. Refer to the
appendix
Pulse Input Modules List
(p. 646)
for information on peripheral terminal
expansion modules available for converting low-level ac signals to square-wave
signals.
8.1.3.3 High-Frequency Measurements
High-frequency (square-wave) signals can be measured on
P
or
C
terminals.
Common sensors that output high-frequency include:
•
Photo-chopper anemometers
•
Flow meters
Measurements include counts, frequency in hertz, and running average. Refer to
the section
Frequency Resolution
(p. 353)
for information about how the resolution
of a frequency measurement can be different depending on whether the
measurement is made with the
PulseCount()
or
TimerIO()
instruction.
•
P Terminals
•
Maximum input frequency = 250 kHz
•
CRBasic instructions:
PulseCount()
High-frequency pulse inputs are routed to an inverting CMOS input buffer with
input hysteresis. The CMOS input buffer is at output
0
level with inputs
≥
2.2 V
and at output
1
level with inputs
≤
0.9 V. An internal 100 k
Ω
resistor is
automatically connected to the terminal to pull it up to 5 Vdc. This pull-up
resistor accommodates open-collector (open-drain) output devices.
C Terminals
•
Maximum input frequency = <1 kHz
•
CRBasic instructions:
PulseCount(), TimerIO()
8.1.3.3.1 Frequency Resolution
Resolution of a frequency measurement made with the
PulseCount()
instruction
is calculated as
353
Summary of Contents for CR1000
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 36: ......
Page 38: ......
Page 40: ......
Page 60: ...Section 4 System Quickstart Figure 16 PC200W View Line Graph 60 ...
Page 96: ......
Page 98: ...98 ...
Page 302: ......
Page 453: ...Section 8 Operation Figure 115 Using the Keyboard Display 453 ...
Page 456: ...Section 8 Operation Figure 118 Real Time Custom 456 ...
Page 457: ...Section 8 Operation 8 8 1 3 Final Memory Tables Figure 119 Final Memory Tables 457 ...
Page 458: ...Section 8 Operation 8 8 2 Run Stop Program Figure 120 Run Stop Program 458 ...
Page 460: ...Section 8 Operation Figure 122 File Edit 460 ...
Page 461: ...Section 8 Operation 8 8 4 PCCard Memory Card Display Figure 123 PCCard CF Card Display 461 ...
Page 478: ......
Page 506: ......
Page 536: ......
Page 636: ......
Page 642: ......
Page 644: ......
Page 676: ......
Page 677: ......