Appendix B. Status, Settings, and Data Table Information (Status/Settings/DTI)
(disabled)
CommsMemAlloc
Settings Editor:
Communication Allocation
AKA:
PakBusNodes
,
PakBus Nodes Allocation
,
PakBus Network Node Number
Keyboard:
Settings (General)
≈ line 7
CRBasic:
variable = settings.keyword
;
SetSettings()
Specifies the amount of memory that the CR1000
allocates for maintaining PakBus routing
information. Represents roughly the maximum
number of PakBus nodes that the CR1000 is able to
track in its routing tables (see section
CommsMemFree(2)
(p. 492)
).
read/write
LONG
At start up,
with no
TCP/IP
comms:
1530
Signifies IP
packets:
• 15 big
• 30 little
• nothing in
receive
queue
CommsMemFree(1)
Keyboard:
Status Table
≈ line 33
CRBasic:
variable = status.keyword
Array indicating numbers of buffers used in
communications except with an external keyboard
display. Two digits per each buffer-size category.
Least significant digit specifies the number of the
smallest buffers. Most significant digit specifies the
number of the largest buffers. When TLS is not
active, there are four categories, "tiny", "little",
"medium", and "large". When TLS is active, there is
an additional fifth category, "huge", and there are
more buffers allocated for each category. See
section
CommsMemFree(1)
(p. 491).
read only
LONG
?
TLS Not
Active:
tiny — 05
little — 15
medium —
25
large — 15
huge — 0
TLS Active:
tiny — 160
little — 99
medium —
99
large — 30
huge — 02
CommsMemFree(2)
Keyboard:
Status Table
≈ line 34
CRBasic:
variable = status.keyword
Array indicating numbers of buffers remaining for
PakBus routing and neighbor lists. Each route or
neighbor requires one buffer. See section
CommsMemFree(2)
(p. 492).
read only
LONG
?
?
CommsMemFree(3)
Keyboard:
Status Table
≈ line 35
CRBasic:
variable = status.keyword
Array indicating three two-digit fields, from right
(least significant) to left (most significant): "little"
IP packets available, "big" IP packets, and received
IP packets in a receive queue that have not yet been
processed. See the section
CommsMemFree(3)
(p.
read only
LONG
At start up,
with no
TCP/IP
comms: 1530
— 30 little,
15 big IP
packets
available with
nothing in the
receive
queue.
CompileResults
Station Status:
Results for Last Program Compiled
Keyboard:
Status Table
≈ line 23
CRBasic:
variable = status.keyword
Contains error messages generated at compilation or
during runtime.
read-only
STRING
0
614
Summary of Contents for CR1000
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 36: ......
Page 38: ......
Page 40: ......
Page 60: ...Section 4 System Quickstart Figure 16 PC200W View Line Graph 60 ...
Page 96: ......
Page 98: ...98 ...
Page 302: ......
Page 453: ...Section 8 Operation Figure 115 Using the Keyboard Display 453 ...
Page 456: ...Section 8 Operation Figure 118 Real Time Custom 456 ...
Page 457: ...Section 8 Operation 8 8 1 3 Final Memory Tables Figure 119 Final Memory Tables 457 ...
Page 458: ...Section 8 Operation 8 8 2 Run Stop Program Figure 120 Run Stop Program 458 ...
Page 460: ...Section 8 Operation Figure 122 File Edit 460 ...
Page 461: ...Section 8 Operation 8 8 4 PCCard Memory Card Display Figure 123 PCCard CF Card Display 461 ...
Page 478: ......
Page 506: ......
Page 536: ......
Page 636: ......
Page 642: ......
Page 644: ......
Page 676: ......
Page 677: ......