Appendix B. Status, Settings, and Data Table Information (Status/Settings/DTI)
IPTraceCode
Settings Editor:
IP Trace Code
Keyboard:
Settings (TCP/IP)
≈ line 31
CRBasic:
variable = settings.keyword
;
SetSettings()
This setting controls what type of information is sent
on the port specified by
IPTracePort
and via Telnet.
Useful values are:
0 Trace is inactive
1 Startup and watchdog only
2 Verbose PPP
4 Print general informational messages
16 Display net-interface error messages
256 Transport protocol (UDP/TCP/RVD) trace
8192
FTP trace
65535
Trace everything
read/write
UINT2
0
0 to 65535,
see
description at
left.
IPTraceComport
Settings Editor:
IP Trace COM Port
Aliased from:
IPTrace
Keyboard:
Settings (TCP/IP)
≈ line 30
CRBasic:
variable = settings.keyword
;
SetSettings()
Specifies the port (if any) on which TCP/IP trace
information is sent. Information type is controlled
by
IPTraceCode
.
read/write
LONG
0 (inactive)
0 to 65535
IsRouter
Settings Editor:
Is Router
Keyboard:
Settings (General)
≈ line 6
CRBasic:
variable = settings.keyword
;
SetSettings()
Controls configuration of CR1000 as a router or leaf
node.
read/write
BOOLEAN
False
True
= router
False
=leaf
node
Table 176.
Status/Settings/DTI: L
Keyword
Alias,
Access,
Description
Read/Write,
DataType,
Units
Default
Value
Normal
Range
LastSlowScan()
Keyboard:
Status Table
≈ line 45
CRBasic:
variable = status.keyword
Reports the las time a
SlowSequence
scan in the
CRBasic program was executed. See
MaxSlowProcTime
(p. 620),
SkippedSlowScan
(p. 628),
SlowProcTime
(p. 629).
read only
NSEC array
date/time
n/a
recent past
LastSystemScan
Keyboard:
Status Table
≈ line 44
CRBasic:
variable = status.keyword
Reports the time of the of the last auto (background)
calibration, which runs in a hidden slow-sequence
type scan. See MaxSystemProcTime
(p. 621),
SkippedSystemScan
(p. 628),
SystemProcTime
(p.
and section CR1000 Auto Calibration —
Overview
(p. 92).
read-only
NSEC
date/time
n/a
within the
past few
minutes
LithiumBattery
Station Status:
Lithium Battery
Keyboard:
Status Table
≈ line 17
CRBasic:
variable = status.keyword
Voltage of the internal lithium battery. Updated in
auto (background) calibration. Replace lithium
battery if <2.7 Vdc. See Replacing the Internal
read-only
FLOAT
volts
n/a
2.7 to 3.6
619
Summary of Contents for CR1000
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 36: ......
Page 38: ......
Page 40: ......
Page 60: ...Section 4 System Quickstart Figure 16 PC200W View Line Graph 60 ...
Page 96: ......
Page 98: ...98 ...
Page 302: ......
Page 453: ...Section 8 Operation Figure 115 Using the Keyboard Display 453 ...
Page 456: ...Section 8 Operation Figure 118 Real Time Custom 456 ...
Page 457: ...Section 8 Operation 8 8 1 3 Final Memory Tables Figure 119 Final Memory Tables 457 ...
Page 458: ...Section 8 Operation 8 8 2 Run Stop Program Figure 120 Run Stop Program 458 ...
Page 460: ...Section 8 Operation Figure 122 File Edit 460 ...
Page 461: ...Section 8 Operation 8 8 4 PCCard Memory Card Display Figure 123 PCCard CF Card Display 461 ...
Page 478: ......
Page 506: ......
Page 536: ......
Page 636: ......
Page 642: ......
Page 644: ......
Page 676: ......
Page 677: ......